Inspection Status: Denied
Inspection History: SIGN SHOP
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/31/2008 | SIGN SHOP | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. UNTIE SHIPPING KNOTS IN GTO CABLES 2. TAKE UP SLACK GTO IN TRANSFORMER ENCLOSURE 3. PROPERLY GROUND ENCLOSURE 4. SIGN TO BE SWITCHED PER 600.6 5. CHECK REAR SIGN NEXT TIME 6. DO NOT ENERGIZE SIGN UNTIL FINALED BY ELECTRICAL INSPECTOR 7. A SERVICE LIGHT IS NEEDED |