Permit: T06OT03000

Parcel: 12510004B

Inspection Status: Denied

Inspection History: SIGN SHOP

Permit Number - T06OT03000

Inspection Description - SIGN SHOP

Inspection Status - Denied

Date Description Inspector Results Comments
07/31/2008 SIGN SHOP Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. UNTIE SHIPPING KNOTS IN GTO CABLES
2. TAKE UP SLACK GTO IN TRANSFORMER ENCLOSURE
3. PROPERLY GROUND ENCLOSURE
4. SIGN TO BE SWITCHED PER 600.6
5. CHECK REAR SIGN NEXT TIME
6. DO NOT ENERGIZE SIGN UNTIL FINALED BY ELECTRICAL INSPECTOR
7. A SERVICE LIGHT IS NEEDED