Permit: T06OT01406
Permit Details
Apply Date:
05/25/2006
Applicant:
WESTERN HERITAGE HOMES
Description:
11063
Contractors:
- WESTERN HERITAGE HOMES L L C
Outstanding Inspections
Permit Status: Expired
Permit Number: T06OT01406
Permite Description: 11063
Total Outstanding Inspections - 2
| Last Inspection Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/21/2006 | SIGN SHOP | N/A | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
| 07/21/2006 | SIGN ELECTRIC | N/A | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* |
Completed Inspections
Permit Status: Expired
Permit Number: T06OT01406
Permit Description: 11063
Total Completed Inspections - 3
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/26/2006 | SIGN SITE REVIEW | JSONKIN | Approved | |
| 06/27/2006 | SIGN EXCAVATION | JSONKIN | Approved | IVRS - Inspection :* MAKE SURE SIGN SETBACK IS AS PER APPROVED PLAN. |
| 07/21/2006 | SIGN INSPECTION | JSONKIN | Approved | IVRS - Inspection :* 1. A MARKING LABEL IS NEEDED 600.4 2. A DISCONNECTING MEANS IS NEEDED 600.6 3. WE HAVE MULTIPLE TERMINATION AT LUGS IN TIME CLOCK 4. SUPPORT CONDUIT 5. UNCOVER UNDERGROUND TO INSPECT 6. FITTINGS TO BE LISTED FOR WEATHERPROOF LOCATION 7. USE CORRECT AMPACITY BREAKER FOR CONDUCTOR. |