Inspection History Details
Inspection Status: Approved
Inspection History: SIGN INSPECTION
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/21/2006 | SIGN INSPECTION | Approved | IVRS - Inspection :* 1. A MARKING LABEL IS NEEDED 600.4 2. A DISCONNECTING MEANS IS NEEDED 600.6 3. WE HAVE MULTIPLE TERMINATION AT LUGS IN TIME CLOCK 4. SUPPORT CONDUIT 5. UNCOVER UNDERGROUND TO INSPECT 6. FITTINGS TO BE LISTED FOR WEATHERPROOF LOCATION 7. USE CORRECT AMPACITY BREAKER FOR CONDUCTOR. |