Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit: T06OT01406

Parcel: 128111090


Addresses:

221 S SWAN RD

Inspection Status: Approved

Inspection History: SIGN INSPECTION

Date Description Inspector Results Comments
07/21/2006 SIGN INSPECTION Approved IVRS - Inspection :*
1. A MARKING LABEL IS NEEDED 600.4
2. A DISCONNECTING MEANS IS NEEDED 600.6
3. WE HAVE MULTIPLE TERMINATION AT LUGS IN TIME CLOCK
4. SUPPORT CONDUIT
5. UNCOVER UNDERGROUND TO INSPECT
6. FITTINGS TO BE LISTED FOR WEATHERPROOF LOCATION
7. USE CORRECT AMPACITY BREAKER FOR CONDUCTOR.