Permit: T06OT00929
Permit Details
Apply Date:
04/04/2006
Applicant:
L A SPAS
Description:
WAREHOUSE W/RETAIL SALES AND OFFICE: 82' x 155' BUILDING, WAREHOUSE AREA (120' x 82' ) W/ OL = 19, SALES AREA (1342 SF) W/ O.L. = 44, OFFICE AREA (646 SF) W/ O.L. = 6.
Permit Reviews
Permit Number - T06OT00929
Permit Status: Expired
Permit Description: WAREHOUSE W/RETAIL SALES AND OFFICE:
82' x 155' BUILDING, WAREHOUSE AREA (120' x 82' ) W/ OL = 19, SALES AREA (1342 SF) W/ O.L. = 44, OFFICE AREA (646 SF) W/ O.L. = 6.
| Start Date | Submittal | Complete Date | Status |
|---|---|---|---|
| 04/04/2006 | C OF O | 04/11/2006 | COMPLETED |
Outstanding Inspections
Permit Status: Expired
Permit Number: T06OT00929
Permite Description: WAREHOUSE W/RETAIL SALES AND OFFICE:
82' x 155' BUILDING, WAREHOUSE AREA (120' x 82' ) W/ OL = 19, SALES AREA (1342 SF) W/ O.L. = 44, OFFICE AREA (646 SF) W/ O.L. = 6.
Total Outstanding Inspections - 4
| Last Inspection Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/12/2006 | BUILDING - FINAL | N/A | Not ready for Inspection | IVRS - Inspection :* * NEED PLUMBING & ELECTRIC FINALS IN ORDER TO APPROVE PLEASE RE-CALL WHEN READY FOR BUILDING FINAL. |
| 04/12/2006 | ELECTRIC - FINAL | N/A | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. EXTENSION CORD USE AT DESK AREA - FRONT MUST BE REMOVED AND PERMANENT MEANS USED. 2. SAME SITUATION IN ELECTRICAL PANELS AREA - EXTENSION CORD USE TO BE REMOVED AND PERMANENT MEANS USED. 3. EXTENSION CORD USE AROUND SPAS TO BE MADE PERMANENT. 4. EXTENSION CORD GOING UP THRU ACCESS DOOR TO ROOF - USE PERMANENT MEANS. 5. 50 AMP SO CORD FROM PANEL A GOING THRU WALL TO SHOW ROOM SAME PROBLEM AS #5 ABOVE, ALSO EXTENSION CORD USE CANNOT BE USED AS PERMANENT WIRING MEANS. 7. OPEN ELECT BOX AT RAMP AREA OF WAREHOUSE MOST OF THESE VIOLATIONS ARE LISTED AS NOT PERMITTED AS PER 2002 NATIONAL ELECTRIC CODE SECTION 400 - CORD USAGE. |
| 04/12/2006 | PLUMBING - FINAL | N/A | Not ready for Inspection | IVRS - Inspection :* 1. SUPPORT GAS PIPING AT ROOFTOP UNIT. 2. PROVIDE BACKFLOW PROTECTION FOR SOURCE OF WATER TO FILL SPAS 3. PROVIDE FLOOR DRAIN STRAINER COVER IN JANITOR CLOSET TO AVOID TRIPPING HAZARD. 4. PROVIDE VACUUM BREAKERS FOR ALL HOSE BIBBS. |
| 04/12/2006 | SIGN - FINAL | N/A | Denied | IVRS - Inspection : SEVERAL SIGNS ON SITE W/O PERMITS; SITE IS OVER SIGN ALLOWANCE AND MUST REMOVE SOME SIGNAGE The occupancy inspection reveals that corrections are required. Please furni |
Completed Inspections
Permit Status: Expired
Permit Number: T06OT00929
Permit Description: WAREHOUSE W/RETAIL SALES AND OFFICE:
82' x 155' BUILDING, WAREHOUSE AREA (120' x 82' ) W/ OL = 19, SALES AREA (1342 SF) W/ O.L. = 44, OFFICE AREA (646 SF) W/ O.L. = 6.
Total Completed Inspections - 2
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/12/2006 | MECHANICAL - FINAL | JMILITEL | Approved | IVRS - Inspection :* OK FOR FINAL |
| 04/12/2006 | FIRE - FINAL | LTHOMAS | Approved |