Permit Details

Status:
Expired
Type:
COMMERCIAL OTHER
Address NEW:
4721 E BROADWAY BL
Apply Date:
04/04/2006
Applicant:
L A SPAS
Description:
WAREHOUSE W/RETAIL SALES AND OFFICE: 82' x 155' BUILDING, WAREHOUSE AREA (120' x 82' ) W/ OL = 19, SALES AREA (1342 SF) W/ O.L. = 44, OFFICE AREA (646 SF) W/ O.L. = 6.

Permit Reviews

Permit Number - T06OT00929
Permit Status: Expired
Permit Description: WAREHOUSE W/RETAIL SALES AND OFFICE: 82' x 155' BUILDING, WAREHOUSE AREA (120' x 82' ) W/ OL = 19, SALES AREA (1342 SF) W/ O.L. = 44, OFFICE AREA (646 SF) W/ O.L. = 6.
Start Date Submittal Complete Date Status  
04/04/2006 C OF O 04/11/2006 COMPLETED Review Details

Outstanding Inspections

Permit Status: Expired
Permit Number: T06OT00929
Permite Description: WAREHOUSE W/RETAIL SALES AND OFFICE: 82' x 155' BUILDING, WAREHOUSE AREA (120' x 82' ) W/ OL = 19, SALES AREA (1342 SF) W/ O.L. = 44, OFFICE AREA (646 SF) W/ O.L. = 6.
Total Outstanding Inspections - 4
Last Inspection Date Description Inspector Results Comments
04/12/2006 BUILDING - FINAL N/A Not ready for Inspection IVRS - Inspection :*
* NEED PLUMBING & ELECTRIC FINALS IN ORDER TO APPROVE PLEASE RE-CALL WHEN READY FOR BUILDING FINAL.
04/12/2006 ELECTRIC - FINAL N/A Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. EXTENSION CORD USE AT DESK AREA - FRONT MUST BE REMOVED AND PERMANENT MEANS USED.
2. SAME SITUATION IN ELECTRICAL PANELS AREA - EXTENSION CORD USE TO BE REMOVED AND PERMANENT MEANS USED.
3. EXTENSION CORD USE AROUND SPAS TO BE MADE PERMANENT.
4. EXTENSION CORD GOING UP THRU ACCESS DOOR TO ROOF - USE PERMANENT MEANS.
5. 50 AMP SO CORD FROM PANEL A GOING THRU WALL TO SHOW ROOM SAME PROBLEM AS #5 ABOVE, ALSO EXTENSION CORD USE CANNOT BE USED AS PERMANENT WIRING MEANS.
7. OPEN ELECT BOX AT RAMP AREA OF WAREHOUSE MOST OF THESE VIOLATIONS ARE LISTED AS NOT PERMITTED AS PER 2002 NATIONAL ELECTRIC CODE SECTION 400 - CORD USAGE.
04/12/2006 PLUMBING - FINAL N/A Not ready for Inspection IVRS - Inspection :*
1. SUPPORT GAS PIPING AT ROOFTOP UNIT.
2. PROVIDE BACKFLOW PROTECTION FOR SOURCE OF WATER TO FILL SPAS
3. PROVIDE FLOOR DRAIN STRAINER COVER IN JANITOR CLOSET TO AVOID TRIPPING HAZARD.
4. PROVIDE VACUUM BREAKERS FOR ALL HOSE BIBBS.
04/12/2006 SIGN - FINAL N/A Denied IVRS - Inspection : SEVERAL SIGNS ON SITE W/O PERMITS; SITE IS OVER SIGN ALLOWANCE AND MUST REMOVE SOME SIGNAGE
The occupancy inspection reveals that corrections are required. Please furni

Completed Inspections

Permit Status: Expired
Permit Number: T06OT00929
Permit Description: WAREHOUSE W/RETAIL SALES AND OFFICE: 82' x 155' BUILDING, WAREHOUSE AREA (120' x 82' ) W/ OL = 19, SALES AREA (1342 SF) W/ O.L. = 44, OFFICE AREA (646 SF) W/ O.L. = 6.
Total Completed Inspections - 2
Date Description Inspector Results Comments
04/12/2006 MECHANICAL - FINAL JMILITEL Approved IVRS - Inspection :*
OK FOR FINAL
04/12/2006 FIRE - FINAL LTHOMAS Approved

Documents

File Name Document Type  
None DOCUMENTS VIEW
None CONSTRPLANS VIEW
None SIGNS VIEW