Inspection History Details
Inspection Status: Denied
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/12/2006 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. EXTENSION CORD USE AT DESK AREA - FRONT MUST BE REMOVED AND PERMANENT MEANS USED. 2. SAME SITUATION IN ELECTRICAL PANELS AREA - EXTENSION CORD USE TO BE REMOVED AND PERMANENT MEANS USED. 3. EXTENSION CORD USE AROUND SPAS TO BE MADE PERMANENT. 4. EXTENSION CORD GOING UP THRU ACCESS DOOR TO ROOF - USE PERMANENT MEANS. 5. 50 AMP SO CORD FROM PANEL A GOING THRU WALL TO SHOW ROOM SAME PROBLEM AS #5 ABOVE, ALSO EXTENSION CORD USE CANNOT BE USED AS PERMANENT WIRING MEANS. 7. OPEN ELECT BOX AT RAMP AREA OF WAREHOUSE MOST OF THESE VIOLATIONS ARE LISTED AS NOT PERMITTED AS PER 2002 NATIONAL ELECTRIC CODE SECTION 400 - CORD USAGE. |