Permit Details

Status:
Final
Type:
SINGLE FAMILY OTHER
Address:
7232 E 19TH ST
Address NEW:
7232 E 19TH ST
Apply Date:
12/06/2006
Applicant:
ALASKAN QUALITY SERVICES INC
Description:
GAS PAC:REPLACEMENT
Contractors:
  • ALASKAN QUALITY SERVICES INC

Permit Reviews

Permit Number - T06ME00721
Permit Status: Final
Permit Description: GAS PAC:REPLACEMENT
Start Date Submittal Complete Date Status  
12/06/2006 MECHANICAL 12/06/2006 COMPLETED Review Details

Outstanding Activity Conditions

Permit Number - T06ME00721
Permit Status: Final
Permit Description: GAS PAC:REPLACEMENT
Total Outstanding Activity Conditions - 1
Date Name
12/06/2006 PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION.

Completed Inspections

Permit Status: Final
Permit Number: T06ME00721
Permit Description: GAS PAC:REPLACEMENT
Total Completed Inspections - 3
Date Description Inspector Results Comments
12/11/2006 MECHANICAL - FINAL JMILITEL Approved IVRS - Inspection :
See detailed listing on site.| 999*
1. TERMINATE CONDENSATE TO WITHIN 6" OF THE GROUND WITH AN ELBOW & NIPPLE DIVERT WATER AWAY FROM HOUSE. PAINT PVC W/LATEX PAINT. BLOCK & CLAMP EVERY 4'.
2. LOW VOLTAGE WIRE NEEDS TO BE IN CONDUIT.
3. WAS 2" DUCT LINES USED ON EXPOSED DUCT ON ROOF?
INSULATION MUST BE MIN. R-8
4. PROVIDE A PRESSURE TEST ON ALL NEW GAS PIPING. NEED TO SEE GAS PIPE CONNECTION INSIDE HOUSE.
5. DO NOT USE WHITE WIRE FOR POWER. WHITE INDICATES NEUTRAL.
6. NEED TO SEE CIRCUIT BREAKER. BE SURE ANY SERVICE UPGRADE TO 200 AMPS HAS A PERMIT.
12/11/2006 MECHANICAL - INTERMEDIATE JMILITEL Approved IVRS - Inspection :
See detailed listing on site.| 999*
04/30/2007 PERMIT FINALED BFLORES Approved