Permit: T06ME00721

Parcel: 134160490


Addresses:

7232 E 19TH ST

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
04/26/2007 MECHANICAL - FINAL Approved IVRS - Inspection :*
CORRECTIONS HAVE BEEN MADE
04/10/2007 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
COVER ALL INSULATION EXPOSED TO WEATHER.
THIS INCLUDES THE UNDER SIDE.
TAPE COVERED WITH DUCT SEALER IS NOT ACCEPTABLE
REMOVE ALL TAPE
PROVIDE SCREWS IN ALL JOINTS & SEAMS
03/29/2007 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
INSPECTED INSULATION AROUND EXPOSED DUCT ON ROOF
OK TO COVER WITH SHEET METAL
RECALL FOR FINAL INSPECTION
FOIL WRAP ALONE NOT APPROVED FOR OUTDOORS.
01/24/2007 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
12/11/2006 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. TERMINATE CONDENSATE TO WITHIN 6" OF THE GROUND WITH AN ELBOW & NIPPLE DIVERT WATER AWAY FROM HOUSE. PAINT PVC W/LATEX PAINT. BLOCK & CLAMP EVERY 4'.
2. LOW VOLTAGE WIRE NEEDS TO BE IN CONDUIT.
3. WAS 2" DUCT LINES USED ON EXPOSED DUCT ON ROOF?
INSULATION MUST BE MIN. R-8
4. PROVIDE A PRESSURE TEST ON ALL NEW GAS PIPING. NEED TO SEE GAS PIPE CONNECTION INSIDE HOUSE.
5. DO NOT USE WHITE WIRE FOR POWER. WHITE INDICATES NEUTRAL.
6. NEED TO SEE CIRCUIT BREAKER. BE SURE ANY SERVICE UPGRADE TO 200 AMPS HAS A PERMIT.