Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/26/2007 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* CORRECTIONS HAVE BEEN MADE |
|
| 04/10/2007 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* COVER ALL INSULATION EXPOSED TO WEATHER. THIS INCLUDES THE UNDER SIDE. TAPE COVERED WITH DUCT SEALER IS NOT ACCEPTABLE REMOVE ALL TAPE PROVIDE SCREWS IN ALL JOINTS & SEAMS |
|
| 03/29/2007 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* INSPECTED INSULATION AROUND EXPOSED DUCT ON ROOF OK TO COVER WITH SHEET METAL RECALL FOR FINAL INSPECTION FOIL WRAP ALONE NOT APPROVED FOR OUTDOORS. |
|
| 01/24/2007 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 12/11/2006 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. TERMINATE CONDENSATE TO WITHIN 6" OF THE GROUND WITH AN ELBOW & NIPPLE DIVERT WATER AWAY FROM HOUSE. PAINT PVC W/LATEX PAINT. BLOCK & CLAMP EVERY 4'. 2. LOW VOLTAGE WIRE NEEDS TO BE IN CONDUIT. 3. WAS 2" DUCT LINES USED ON EXPOSED DUCT ON ROOF? INSULATION MUST BE MIN. R-8 4. PROVIDE A PRESSURE TEST ON ALL NEW GAS PIPING. NEED TO SEE GAS PIPE CONNECTION INSIDE HOUSE. 5. DO NOT USE WHITE WIRE FOR POWER. WHITE INDICATES NEUTRAL. 6. NEED TO SEE CIRCUIT BREAKER. BE SURE ANY SERVICE UPGRADE TO 200 AMPS HAS A PERMIT. |