Permit: T06ME00709
Permit Details
Apply Date:
12/01/2006
Applicant:
A A A REFRIGERATION
Description:
A/C & FURNACE:REPLACE GASPAC W/3-1/2 TON
Contractors:
- A A A REFRIGERATION
Permit Reviews
Permit Number - T06ME00709
Permit Status: Expired
Permit Description: A/C & FURNACE:REPLACE GASPAC W/3-1/2 TON
| Start Date | Submittal | Complete Date | Status |
|---|---|---|---|
| 12/01/2006 | MECHANICAL | 12/01/2006 | COMPLETED |
Outstanding Activity Conditions
Permit Number - T06ME00709
Permit Status: Expired
Permit Description: A/C & FURNACE:REPLACE GASPAC W/3-1/2 TON
Total Outstanding Activity Conditions - 1
| Date | Name |
|---|---|
| 12/01/2006 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Outstanding Inspections
Permit Status: Expired
Permit Number: T06ME00709
Permite Description: A/C & FURNACE:REPLACE GASPAC W/3-1/2 TON
Total Outstanding Inspections - 1
| Last Inspection Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/11/2006 | MECHANICAL - FINAL | N/A | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. GAS LINE NOT HOLDING PRESSURE. 2. SECURE GAS LINE TO WALL. 3. CONDENSATE MUST TERMINATE WITHIN 6" OF THE GROUND WITH AN ELBOW & A NIPPLE TO DIVERT WATER AWAY FROM HOUSE. |