Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit: T06ME00378
Permit Details
Apply Date:
07/12/2006
Applicant:
RITE WAY VENTILATING CO , *C
Description:
INST: 5 TON PACKAGE UNIT (APA)
Contractors:
- RITE WAY VENTILATING CO , *C
Outstanding Activity Conditions
Permit Number - T06ME00378
Permit Status: Closed
Permit Description: INST: 5 TON PACKAGE UNIT (APA)
Total Outstanding Activity Conditions - 1
Date | Name |
---|---|
07/12/2006 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Completed Inspections
Permit Status: Closed
Permit Number: T06ME00378
Permit Description: INST: 5 TON PACKAGE UNIT (APA)
Total Completed Inspections - 2
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
07/25/2006 | MECHANICAL - FINAL | JMILITEL | Approved | IVRS - Inspection : See detailed listing on site.| 999* CONDENSATE CANNOT TERMINATE INTO A SEWER VENT. PROVIDE A TRAP TIGHTEN LOOSE ELEC. CONNECTIONS TO UNIT & DISCONNECT IDENTIFY HEAT STRIP INSTALLED 60 AMP. BREAKER MAY NOT HANDLE THE ENTIRE LOAD. SUPPORT ELEC. CONDUITS ON ROOF. |
02/19/2010 | MECHANICAL - INTERMEDIATE | LHANLY | Approved |