Permit: T06ME00378

Parcel: 133403070


Addresses:

7815 E HAWTHORNE ST

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
02/19/2010 MECHANICAL - FINAL Approved
07/25/2006 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
CONDENSATE CANNOT TERMINATE INTO A SEWER VENT. PROVIDE A TRAP
TIGHTEN LOOSE ELEC. CONNECTIONS TO UNIT & DISCONNECT
IDENTIFY HEAT STRIP INSTALLED
60 AMP. BREAKER MAY NOT HANDLE THE ENTIRE LOAD.
SUPPORT ELEC. CONDUITS ON ROOF.