Permit: T06ME00325
Permit Details
Apply Date:
06/20/2006
Applicant:
RITE WAY VENTILATING CO , *C
Description:
REPLACE:4 TON GAS PK APA
Contractors:
- RITEWAY VENTILATING CO. *C*
Outstanding Activity Conditions
Permit Number - T06ME00325
Permit Status: Expired
Permit Description: REPLACE:4 TON GAS PK APA
Total Outstanding Activity Conditions - 1
Date | Name |
---|---|
06/20/2006 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Outstanding Inspections
Permit Status: Expired
Permit Number: T06ME00325
Permite Description: REPLACE:4 TON GAS PK APA
Total Outstanding Inspections - 1
Last Inspection Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/04/2006 | MECHANICAL - FINAL | N/A | Denied | IVRS - Inspection : See detailed listing on site.| 999* WHAT SIZE HEAT STRIP IS INSTALLED? MARK UNIT DATA PLATE ACCORDINGLY. CONDENSATE CANNOT DRIP OUT OF A ROOF SCUPPER. TERMINATE TO WITHIN 6" OFF THE GROUND WITH AN ELBOW & NIPPLE. DIVERT THE WATER AWAY FROM THE FOUNDATION. 50 AMP. BREAKER NOT ADEQUATE FOR THE A/C WITH HEAT STRIP. #4 ALUMINUM WIRE ONLY GOOD FOR 60 AMP. BREAKER NEEDS TO BE AT LEAST 70 AMP. |