Permit: T06ME00325

Parcel: 13607409A


Addresses:

1208 S BROWN AV

Inspection Status: Denied

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
08/04/2006 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
WHAT SIZE HEAT STRIP IS INSTALLED? MARK UNIT DATA PLATE ACCORDINGLY.
CONDENSATE CANNOT DRIP OUT OF A ROOF SCUPPER.
TERMINATE TO WITHIN 6" OFF THE GROUND WITH AN ELBOW & NIPPLE. DIVERT THE WATER AWAY FROM THE FOUNDATION.
50 AMP. BREAKER NOT ADEQUATE FOR THE A/C WITH HEAT STRIP. #4 ALUMINUM WIRE ONLY GOOD FOR 60 AMP. BREAKER NEEDS TO BE AT LEAST 70 AMP.