Inspection History Details
Inspection Status: Denied
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/04/2006 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* WHAT SIZE HEAT STRIP IS INSTALLED? MARK UNIT DATA PLATE ACCORDINGLY. CONDENSATE CANNOT DRIP OUT OF A ROOF SCUPPER. TERMINATE TO WITHIN 6" OFF THE GROUND WITH AN ELBOW & NIPPLE. DIVERT THE WATER AWAY FROM THE FOUNDATION. 50 AMP. BREAKER NOT ADEQUATE FOR THE A/C WITH HEAT STRIP. #4 ALUMINUM WIRE ONLY GOOD FOR 60 AMP. BREAKER NEEDS TO BE AT LEAST 70 AMP. |