Permit: T06ME00222
Permit Details
Apply Date:
05/03/2006
Applicant:
DENNIS CRAFT
Description:
REPLACE:4 A/C UNITS
Contractors:
- CONDITIONED AIR MECHANICAL SERVI
Permit Reviews
Permit Number - T06ME00222
Permit Status: Final
Permit Description: REPLACE:4 A/C UNITS
Start Date | Submittal | Complete Date | Status |
---|---|---|---|
05/03/2006 | MECHANICAL | 05/03/2006 | COMPLETED |
Outstanding Activity Conditions
Permit Number - T06ME00222
Permit Status: Final
Permit Description: REPLACE:4 A/C UNITS
Total Outstanding Activity Conditions - 1
Date | Name |
---|---|
05/03/2006 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Completed Inspections
Permit Status: Final
Permit Number: T06ME00222
Permit Description: REPLACE:4 A/C UNITS
Total Completed Inspections - 3
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
12/06/2007 | MECHANICAL - FINAL | JMILITEL | Approved | IVRS - Inspection : See detailed listing on site.| 999* - PROVIDE 1" GAS PIPE TO FURNACES - SUPPORT HIGH VOLTAGE ELEC. CONDUIT - JUNCTION BOX NOT ACCESSIBLE & CANNOT LAY ON THE ROOF - SEAL PENETRATION IN ROOF CURB - RTU 2, 3 PROVIDE MORE SUPPORT UNDER CONDENSATE DRAIN LINES & CLAMP PIPE TO BLOCKS - DISCONNECTS ARE OVERFUSED - RTU 2 NUMBER ON UNIT DOES NOT MATCH NUMBER ON DISCONNECT - RECALL FOR FINAL |
01/25/2008 | MECHANICAL - INTERMEDIATE | JMILITEL | Approved | |
01/28/2008 | PERMIT FINALED | BFLORES | Approved |