Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Details

Status:
Final
Type:
COMMERCIAL OTHER
Apply Date:
05/03/2006
Applicant:
DENNIS CRAFT
Description:
REPLACE:4 A/C UNITS
Contractors:
  • CONDITIONED AIR MECHANICAL SERVI

Permit Reviews

Permit Number - T06ME00222
Permit Status: Final
Permit Description: REPLACE:4 A/C UNITS
Start Date Submittal Complete Date Status  
05/03/2006 MECHANICAL 05/03/2006 COMPLETED Review Details

Outstanding Activity Conditions

Permit Number - T06ME00222
Permit Status: Final
Permit Description: REPLACE:4 A/C UNITS
Total Outstanding Activity Conditions - 1
Date Name
05/03/2006 PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION.

Completed Inspections

Permit Status: Final
Permit Number: T06ME00222
Permit Description: REPLACE:4 A/C UNITS
Total Completed Inspections - 3
Date Description Inspector Results Comments
12/06/2007 MECHANICAL - FINAL JMILITEL Approved IVRS - Inspection :
See detailed listing on site.| 999*
- PROVIDE 1" GAS PIPE TO FURNACES
- SUPPORT HIGH VOLTAGE ELEC. CONDUIT
- JUNCTION BOX NOT ACCESSIBLE & CANNOT LAY ON THE ROOF
- SEAL PENETRATION IN ROOF CURB
- RTU 2, 3 PROVIDE MORE SUPPORT UNDER CONDENSATE DRAIN LINES & CLAMP PIPE TO BLOCKS
- DISCONNECTS ARE OVERFUSED
- RTU 2 NUMBER ON UNIT DOES NOT MATCH NUMBER ON DISCONNECT
- RECALL FOR FINAL
01/25/2008 MECHANICAL - INTERMEDIATE JMILITEL Approved
01/28/2008 PERMIT FINALED BFLORES Approved

Documents

File Name Document Type  
None DOCUMENTS VIEW