Permit: T06EL02399
Permit Details
Status:
Expired
Type:
SINGLE FAMILY OTHER
Address:
255 E DELANO ST #01
Address NEW:
255 E DELANO ST #01
Apply Date:
12/20/2006
Applicant:
MANUEL VARELA
Description:
RELOCATE THE ELECTRIC METER WIRING
Permit Reviews
Permit Number - T06EL02399
Permit Status: Expired
Permit Description: RELOCATE THE ELECTRIC METER WIRING
| Start Date | Submittal | Complete Date | Status |
|---|---|---|---|
| 01/25/2007 | ELECTRICAL | 01/25/2007 | COMPLETED |
| 12/20/2006 | ELECTRICAL | 12/20/2006 | COMPLETED |
Outstanding Activity Conditions
Permit Number - T06EL02399
Permit Status: Expired
Permit Description: RELOCATE THE ELECTRIC METER WIRING
Total Outstanding Activity Conditions - 1
| Date | Name |
|---|---|
| 12/20/2006 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Outstanding Inspections
Permit Status: Expired
Permit Number: T06EL02399
Permite Description: RELOCATE THE ELECTRIC METER WIRING
Total Outstanding Inspections - 2
| Last Inspection Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| ELECTRIC - SERVICE RELOCATION | N/A | Not Inspected | ||
| 03/22/2007 | ELECTRIC - INTERMEDIATE | N/A | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. REMOVE BONDING SCREWS IN SUB-PANELS, NEUTRAL AND GROUNDS TO BE SEPARATED. 2. MULTI-WIRE CKT'S WITH SHARED NEUTRALS TO TERMINATE ON SEPARATE PHASES 3. IDENTIFY PANEL DIRECTORY'S 4. NEED SEALING TYPE LOCKNUTS FOR NIPPLES, GROUND ALL ENCLOSURES AND SEAL UNUSED OPENINGS. 5. USE ONLY BREAKERS LISTED FOR PANEL, SEE PANEL LABEL 6. GROUND FEEDER J-BOX 7. STRAP EMT WITHIN 36" OF BOX & MAX 10' INTERVALS 8. USE OX. INHIBITOR ON ALL ALUMINUM TERMINATIONS 9. MAKE SURE MAX 15 AMP ON 14GA. WIRE & 20 ON 12GA WIRE |
Completed Inspections
Permit Status: Expired
Permit Number: T06EL02399
Permit Description: RELOCATE THE ELECTRIC METER WIRING
Total Completed Inspections - 2
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/15/2007 | ELECTRIC - UNDERGROUND | CCLEMENS | Approved | IVRS - Inspection :* |
| 02/16/2007 | TEP CLEARANCE - AM | BFLORES | Approved | INCR BOTH UNITS 1 & 2 PER C.CLEMENS |