Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Details

Status:
Expired
Type:
SINGLE FAMILY OTHER
Address NEW:
255 E DELANO ST #01
Apply Date:
12/20/2006
Applicant:
MANUEL VARELA
Description:
RELOCATE THE ELECTRIC METER WIRING

Permit Reviews

Permit Number - T06EL02399
Permit Status: Expired
Permit Description: RELOCATE THE ELECTRIC METER WIRING
Start Date Submittal Complete Date Status  
01/25/2007 ELECTRICAL 01/25/2007 COMPLETED Review Details
12/20/2006 ELECTRICAL 12/20/2006 COMPLETED Review Details

Outstanding Activity Conditions

Permit Number - T06EL02399
Permit Status: Expired
Permit Description: RELOCATE THE ELECTRIC METER WIRING
Total Outstanding Activity Conditions - 1
Date Name
12/20/2006 PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION.

Outstanding Inspections

Permit Status: Expired
Permit Number: T06EL02399
Permite Description: RELOCATE THE ELECTRIC METER WIRING
Total Outstanding Inspections - 2
Last Inspection Date Description Inspector Results Comments
ELECTRIC - SERVICE RELOCATION N/A Not Inspected
03/22/2007 ELECTRIC - INTERMEDIATE N/A Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. REMOVE BONDING SCREWS IN SUB-PANELS, NEUTRAL AND GROUNDS TO BE SEPARATED.
2. MULTI-WIRE CKT'S WITH SHARED NEUTRALS TO TERMINATE ON SEPARATE PHASES
3. IDENTIFY PANEL DIRECTORY'S
4. NEED SEALING TYPE LOCKNUTS FOR NIPPLES, GROUND ALL ENCLOSURES AND SEAL UNUSED OPENINGS.
5. USE ONLY BREAKERS LISTED FOR PANEL, SEE PANEL LABEL
6. GROUND FEEDER J-BOX
7. STRAP EMT WITHIN 36" OF BOX & MAX 10' INTERVALS
8. USE OX. INHIBITOR ON ALL ALUMINUM TERMINATIONS
9. MAKE SURE MAX 15 AMP ON 14GA. WIRE & 20 ON 12GA WIRE

Completed Inspections

Permit Status: Expired
Permit Number: T06EL02399
Permit Description: RELOCATE THE ELECTRIC METER WIRING
Total Completed Inspections - 2
Date Description Inspector Results Comments
02/15/2007 ELECTRIC - UNDERGROUND CCLEMENS Approved IVRS - Inspection :*
02/16/2007 TEP CLEARANCE - AM BFLORES Approved INCR BOTH UNITS 1 & 2 PER C.CLEMENS

Documents

File Name Document Type  
None DOCUMENTS VIEW
None CONSTRPLANS VIEW