Inspection Status: Denied
Inspection History: ELECTRIC - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/22/2007 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. REMOVE BONDING SCREWS IN SUB-PANELS, NEUTRAL AND GROUNDS TO BE SEPARATED. 2. MULTI-WIRE CKT'S WITH SHARED NEUTRALS TO TERMINATE ON SEPARATE PHASES 3. IDENTIFY PANEL DIRECTORY'S 4. NEED SEALING TYPE LOCKNUTS FOR NIPPLES, GROUND ALL ENCLOSURES AND SEAL UNUSED OPENINGS. 5. USE ONLY BREAKERS LISTED FOR PANEL, SEE PANEL LABEL 6. GROUND FEEDER J-BOX 7. STRAP EMT WITHIN 36" OF BOX & MAX 10' INTERVALS 8. USE OX. INHIBITOR ON ALL ALUMINUM TERMINATIONS 9. MAKE SURE MAX 15 AMP ON 14GA. WIRE & 20 ON 12GA WIRE |