Permit: T06EL02395
Permit Details
Apply Date:
12/18/2006
Applicant:
D J WILLIAMSON ENTERPRISES INC *C
Description:
UPGRADE: 60 TO 100 AMP (APA)
Contractors:
- D J WILLIAMSON ENTERPRISES INC *C
Outstanding Activity Conditions
Permit Number - T06EL02395
Permit Status: Expired
Permit Description: UPGRADE: 60 TO 100 AMP (APA)
Total Outstanding Activity Conditions - 1
| Date | Name |
|---|---|
| 12/18/2006 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Outstanding Inspections
Permit Status: Expired
Permit Number: T06EL02395
Permite Description: UPGRADE: 60 TO 100 AMP (APA)
Total Outstanding Inspections - 1
| Last Inspection Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| ELECTRIC - SERVICE UPGRADE | N/A | Not Inspected |
Completed Inspections
Permit Status: Expired
Permit Number: T06EL02395
Permit Description: UPGRADE: 60 TO 100 AMP (APA)
Total Completed Inspections - 2
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/22/2006 | ELECTRIC - UNDERGROUND | DSANTACR | Approved | IVRS - Inspection :* 1. 2-GROUND RODS REQUIRED 6' MIN. APART 2. VERIFY WATER & GAS BONDING 3. SUPPORT RISER CONDUIT BELOW ROOF LINE 4. SUPPORT BOX TO WALL & INSTALL BUBBLE TYPE COVER FOR GFI RECEPT UNDER PANEL. 5. ALL CIRCUIT BREAKERS MUST BE SAME BRAND AS PANEL. 6. OUTSIDE J-BOXES MUST BE OUTDOOR RATED 7. GROUND WIRE REQUIRED IN FLEX CONDUIT. ALSO, INSTALL A SEALING LOCKNUT AT PANEL PENETRATION. 8. SUPPORT 1/2" CONDUIT & FLEX 9. RISER SUPPORT ON ROOF MUST BE LISTED, HOMEMADE NOT APPROVED. |
| 01/22/2007 | TEP CLEARANCE - AM | JWEATHER | Approved | INCR CLEARED PER D. SANTACRUZ |