Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - UNDERGROUND
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/19/2007 | ELECTRIC - UNDERGROUND | Approved | IVRS - Inspection :* | |
| 01/11/2007 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* VERIFY SECOND GROUND ROD EXPOSE FOR INSPECTION |
|
| 12/22/2006 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* 1. 2-GROUND RODS REQUIRED 6' MIN. APART 2. VERIFY WATER & GAS BONDING 3. SUPPORT RISER CONDUIT BELOW ROOF LINE 4. SUPPORT BOX TO WALL & INSTALL BUBBLE TYPE COVER FOR GFI RECEPT UNDER PANEL. 5. ALL CIRCUIT BREAKERS MUST BE SAME BRAND AS PANEL. 6. OUTSIDE J-BOXES MUST BE OUTDOOR RATED 7. GROUND WIRE REQUIRED IN FLEX CONDUIT. ALSO, INSTALL A SEALING LOCKNUT AT PANEL PENETRATION. 8. SUPPORT 1/2" CONDUIT & FLEX 9. RISER SUPPORT ON ROOF MUST BE LISTED, HOMEMADE NOT APPROVED. |