Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Details

Status:
Final
Type:
SINGLE FAMILY OTHER
Apply Date:
12/06/2006
Applicant:
JIM JONES
Description:
UPGRADE:ELECTRIC 200AMP

Permit Reviews

Permit Number - T06EL02335
Permit Status: Final
Permit Description: UPGRADE:ELECTRIC 200AMP
Start Date Submittal Complete Date Status  
12/06/2006 ELECTRICAL 12/06/2006 COMPLETED Review Details

Outstanding Activity Conditions

Permit Number - T06EL02335
Permit Status: Final
Permit Description: UPGRADE:ELECTRIC 200AMP
Total Outstanding Activity Conditions - 1
Date Name
12/06/2006 PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION.

Completed Inspections

Permit Status: Final
Permit Number: T06EL02335
Permit Description: UPGRADE:ELECTRIC 200AMP
Total Completed Inspections - 6
Date Description Inspector Results Comments
12/14/2006 ELECTRIC - SERVICE UPGRADE RHOLLAND Approved IVRS - Inspection :*
1. MAINTAIN ALL WORKING CLEARANCES PER 110.26
2. RISER SUPPORTS TO BE 1/4" MINIMUM
3. A PERMANENT METAL ADDRESS LABEL TO BE SCREWED OR RIVETED FOR SERVICE.
4. TIGHTEN LOOSE FITTING
5. USE APPROVED SUPPORT STRAPS AND STRAP AS PER CODES.
6. LABEL ALL BREAKERS.
7. USE APPROVED AND LISTED JUNCTION BOX
8. INSTALL SERVICE FEEDER CONDUCTORS.
9. PROTECT CONDUCTOR AT BACK OF PANEL.
10. BREAKER TO BE SIZED PER CONDUCTOR AMPACITY.
11. CORRECTLY IDENTIFY UNGROUNDED CONDUCTOR.
12. PLEASE VERIFY PERMIT FOR NEW A/C
01/11/2007 ELECTRIC - FINAL RHOLLAND Approved IVRS - Inspection :*
01/11/2007 ELECTRIC - INTERMEDIATE RHOLLAND Approved IVRS - Inspection :*
01/11/2007 ELECTRIC - UNDERGROUND RHOLLAND Approved IVRS - Inspection :*
01/11/2007 TEP CLEARANCE - AM JWEATHER Approved INCR CLEARED PER R. HOLLANDER
01/12/2007 PERMIT FINALED BFLORES Approved