Permit: T06EL02335

Parcel: 133210150

Inspection Status: Approved

Inspection History: ELECTRIC - SERVICE UPGRADE

Date Description Inspector Results Comments
01/11/2007 ELECTRIC - SERVICE UPGRADE Approved IVRS - Inspection :*
01/10/2007 ELECTRIC - SERVICE UPGRADE Partial Approval IVRS - Inspection :*
01/09/2007 ELECTRIC - SERVICE UPGRADE Partial Approval IVRS - Inspection :*
1. FITTINGS TO BE LISTED FOR LOCATION USAGE
2. RECEPTACLE COVER TO BE WEATHERPROOF WHETHER OR NOT PLUGGED INTO 406.8
3. WE NEED A NEW GROUNDING ELECTRODE SYSTEM - 2 GROUND RODS 6' MIN. APART - ALSO, BOND GAS.
12/14/2006 ELECTRIC - SERVICE UPGRADE Not ready for Inspection IVRS - Inspection :*
1. MAINTAIN ALL WORKING CLEARANCES PER 110.26
2. RISER SUPPORTS TO BE 1/4" MINIMUM
3. A PERMANENT METAL ADDRESS LABEL TO BE SCREWED OR RIVETED FOR SERVICE.
4. TIGHTEN LOOSE FITTING
5. USE APPROVED SUPPORT STRAPS AND STRAP AS PER CODES.
6. LABEL ALL BREAKERS.
7. USE APPROVED AND LISTED JUNCTION BOX
8. INSTALL SERVICE FEEDER CONDUCTORS.
9. PROTECT CONDUCTOR AT BACK OF PANEL.
10. BREAKER TO BE SIZED PER CONDUCTOR AMPACITY.
11. CORRECTLY IDENTIFY UNGROUNDED CONDUCTOR.
12. PLEASE VERIFY PERMIT FOR NEW A/C