Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/11/2007 | ELECTRIC - SERVICE UPGRADE | Approved | IVRS - Inspection :* | |
| 01/10/2007 | ELECTRIC - SERVICE UPGRADE | Partial Approval | IVRS - Inspection :* | |
| 01/09/2007 | ELECTRIC - SERVICE UPGRADE | Partial Approval | IVRS - Inspection :* 1. FITTINGS TO BE LISTED FOR LOCATION USAGE 2. RECEPTACLE COVER TO BE WEATHERPROOF WHETHER OR NOT PLUGGED INTO 406.8 3. WE NEED A NEW GROUNDING ELECTRODE SYSTEM - 2 GROUND RODS 6' MIN. APART - ALSO, BOND GAS. |
|
| 12/14/2006 | ELECTRIC - SERVICE UPGRADE | Not ready for Inspection | IVRS - Inspection :* 1. MAINTAIN ALL WORKING CLEARANCES PER 110.26 2. RISER SUPPORTS TO BE 1/4" MINIMUM 3. A PERMANENT METAL ADDRESS LABEL TO BE SCREWED OR RIVETED FOR SERVICE. 4. TIGHTEN LOOSE FITTING 5. USE APPROVED SUPPORT STRAPS AND STRAP AS PER CODES. 6. LABEL ALL BREAKERS. 7. USE APPROVED AND LISTED JUNCTION BOX 8. INSTALL SERVICE FEEDER CONDUCTORS. 9. PROTECT CONDUCTOR AT BACK OF PANEL. 10. BREAKER TO BE SIZED PER CONDUCTOR AMPACITY. 11. CORRECTLY IDENTIFY UNGROUNDED CONDUCTOR. 12. PLEASE VERIFY PERMIT FOR NEW A/C |