Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Details

Status:
Final
Type:
COMMERCIAL OTHER
Address:
700 W WETMORE RD
Address NEW:
700 W WETMORE RD
Apply Date:
12/06/2006
Applicant:
DIVERSIFIED DESIGN AND CONSTRUCT
Description:
ELECTRIC FOR TEMP SALES TRAILER
Contractors:
  • DIVERSIFIED DESIGN AND CONSTRUCT

Permit Reviews

Permit Number - T06EL02332
Permit Status: Final
Permit Description: ELECTRIC FOR TEMP SALES TRAILER
Start Date Submittal Complete Date Status  
12/06/2006 ELECTRICAL 12/06/2006 COMPLETED Review Details

Outstanding Activity Conditions

Permit Number - T06EL02332
Permit Status: Final
Permit Description: ELECTRIC FOR TEMP SALES TRAILER
Total Outstanding Activity Conditions - 1
Date Name
12/06/2006 PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION.

Completed Inspections

Permit Status: Final
Permit Number: T06EL02332
Permit Description: ELECTRIC FOR TEMP SALES TRAILER
Total Completed Inspections - 4
Date Description Inspector Results Comments
12/27/2006 ELECTRIC - FINAL CCLEMENS Approved IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. IDENTIFY PANEL DIRECTORY'S
2. INSTALL PERMANENT IDENTIFICATION LABELS ON PANELS AND DISCONNECT.
3. USE EQUIPMENT GROUND TO GROUND J-BOX
4. SELF TAP SCREWS NOT ALLOWED FOR GROUND CONNECTIONS.
5. SEPARATE NEUTRALS AND GROUNDS IN SUB-PANELS
6. TIGHTEN SET SCREWS ON FEEDER RACEWAY
7. SECURE TRANSFORMER TO SLAB AND INSTALL 3R HOODS
8. PROVIDE PHYSICAL PROTECTION FOR TRANSFORMER & DISCONNECT.
12/27/2006 ELECTRIC - INTERMEDIATE CCLEMENS Approved IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
12/27/2006 ELECTRIC - UNDERGROUND CCLEMENS Approved IVRS - Inspection :*
01/08/2007 PERMIT FINALED BFLORES Approved