Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T06EL02332
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/05/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 12/27/2006 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. IDENTIFY PANEL DIRECTORY'S 2. INSTALL PERMANENT IDENTIFICATION LABELS ON PANELS AND DISCONNECT. 3. USE EQUIPMENT GROUND TO GROUND J-BOX 4. SELF TAP SCREWS NOT ALLOWED FOR GROUND CONNECTIONS. 5. SEPARATE NEUTRALS AND GROUNDS IN SUB-PANELS 6. TIGHTEN SET SCREWS ON FEEDER RACEWAY 7. SECURE TRANSFORMER TO SLAB AND INSTALL 3R HOODS 8. PROVIDE PHYSICAL PROTECTION FOR TRANSFORMER & DISCONNECT. |