Permit: T06EL02332

Parcel: 10408095C


Addresses:

700 W WETMORE RD

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
01/05/2007 ELECTRIC - FINAL Approved IVRS - Inspection :*
12/27/2006 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. IDENTIFY PANEL DIRECTORY'S
2. INSTALL PERMANENT IDENTIFICATION LABELS ON PANELS AND DISCONNECT.
3. USE EQUIPMENT GROUND TO GROUND J-BOX
4. SELF TAP SCREWS NOT ALLOWED FOR GROUND CONNECTIONS.
5. SEPARATE NEUTRALS AND GROUNDS IN SUB-PANELS
6. TIGHTEN SET SCREWS ON FEEDER RACEWAY
7. SECURE TRANSFORMER TO SLAB AND INSTALL 3R HOODS
8. PROVIDE PHYSICAL PROTECTION FOR TRANSFORMER & DISCONNECT.