Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Details

Status:
Final
Type:
COMMERCIAL OTHER
Address:
700 W WETMORE RD
Address NEW:
700 W WETMORE RD
Apply Date:
12/06/2006
Applicant:
DIVERSIFIED DESIGN AND CONSTRUCT
Description:
ELECTRIC FOR TEMP SALES TRAILER
Contractors:
  • DIVERSIFIED DESIGN AND CONSTRUCT

Permit Reviews

Permit Number - T06EL02332
Permit Status: Final
Permit Description: ELECTRIC FOR TEMP SALES TRAILER
Start Date Submittal Complete Date Status  
12/06/2006 ELECTRICAL 12/06/2006 COMPLETED Review Details

Outstanding Activity Conditions

Permit Number - T06EL02332
Permit Status: Final
Permit Description: ELECTRIC FOR TEMP SALES TRAILER
Total Outstanding Activity Conditions - 1
Date Name
12/06/2006 PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION.

Completed Inspections

Permit Status: Final
Permit Number: T06EL02332
Permit Description: ELECTRIC FOR TEMP SALES TRAILER
Total Completed Inspections - 4
Date Description Inspector Results Comments
12/27/2006 ELECTRIC - FINAL CCLEMENS Approved IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. IDENTIFY PANEL DIRECTORY'S
2. INSTALL PERMANENT IDENTIFICATION LABELS ON PANELS AND DISCONNECT.
3. USE EQUIPMENT GROUND TO GROUND J-BOX
4. SELF TAP SCREWS NOT ALLOWED FOR GROUND CONNECTIONS.
5. SEPARATE NEUTRALS AND GROUNDS IN SUB-PANELS
6. TIGHTEN SET SCREWS ON FEEDER RACEWAY
7. SECURE TRANSFORMER TO SLAB AND INSTALL 3R HOODS
8. PROVIDE PHYSICAL PROTECTION FOR TRANSFORMER & DISCONNECT.
12/27/2006 ELECTRIC - INTERMEDIATE CCLEMENS Approved IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
12/27/2006 ELECTRIC - UNDERGROUND CCLEMENS Approved IVRS - Inspection :*
01/08/2007 PERMIT FINALED BFLORES Approved

Documents

File Name Document Type  
None DOCUMENTS VIEW