ELEC UPGRADE 200AMPS
Contractors:
- CUSTOM ELECTRICAL SOLUTIONS
Outstanding Activity Conditions
Permit Number - T06EL02245
Permit Status: Final
Permit Description: ELEC UPGRADE 200AMPS
Total Outstanding Activity Conditions - 1
| Date | Name |
|---|---|
| 11/15/2006 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Completed Inspections
Permit Status: Final
Permit Number: T06EL02245
Permit Description: ELEC UPGRADE 200AMPS
Total Completed Inspections - 4
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/01/2006 | ELECTRIC - SERVICE UPGRADE | DSANTACR | Approved | IVRS - Inspection :* 1. CHASE NIPPLES NOT ALLOWED FOR LB TERMINATION, USE CLOSE NIPPLE WITH LOCKNUTS, BOND BUSHING AT CONCENTRICS. 2. ALL CIRCUIT BREAKERS TO BE OF SAME MANUF. AS PANEL. 3. RISER BRACE ON ROOF MUST BE LISTED, HOMEMADE CONDUIT NOT ACCEPTED. |
| 02/26/2007 | ELECTRIC - FINAL | DSANTACR | Approved | IVRS - Inspection :* |
| 02/27/2007 | PERMIT FINALED | JWEATHER | Approved | |
| 02/27/2007 | TEP CLEARANCE - AM | JWEATHER | Approved | INCR CLEARED PER D. SANTACRUZ |