Permit: T06EL02245

Parcel: 138072440


Addresses:

801 W CALLE MILU

Inspection Status: Approved

Inspection History: ELECTRIC - SERVICE UPGRADE

Date Description Inspector Results Comments
02/26/2007 ELECTRIC - SERVICE UPGRADE Approved IVRS - Inspection :*
12/01/2006 ELECTRIC - SERVICE UPGRADE Partial Approval IVRS - Inspection :*
1. CHASE NIPPLES NOT ALLOWED FOR LB TERMINATION, USE CLOSE NIPPLE WITH LOCKNUTS, BOND BUSHING AT CONCENTRICS.
2. ALL CIRCUIT BREAKERS TO BE OF SAME MANUF. AS PANEL.
3. RISER BRACE ON ROOF MUST BE LISTED, HOMEMADE CONDUIT NOT ACCEPTED.