Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/26/2007 | ELECTRIC - SERVICE UPGRADE | Approved | IVRS - Inspection :* | |
| 12/01/2006 | ELECTRIC - SERVICE UPGRADE | Partial Approval | IVRS - Inspection :* 1. CHASE NIPPLES NOT ALLOWED FOR LB TERMINATION, USE CLOSE NIPPLE WITH LOCKNUTS, BOND BUSHING AT CONCENTRICS. 2. ALL CIRCUIT BREAKERS TO BE OF SAME MANUF. AS PANEL. 3. RISER BRACE ON ROOF MUST BE LISTED, HOMEMADE CONDUIT NOT ACCEPTED. |