Permit: T06EL02229
Permit Details
Apply Date:
11/13/2006
Applicant:
DILLARD SAMUEL JR
Description:
ELEC RECONECT: NOT MOVING METERS
Outstanding Activity Conditions
Permit Number - T06EL02229
Permit Status: Closed
Permit Description: ELEC RECONECT: NOT MOVING METERS
Total Outstanding Activity Conditions - 1
| Date | Name |
|---|---|
| 11/13/2006 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Outstanding Inspections
Permit Status: Closed
Permit Number: T06EL02229
Permite Description: ELEC RECONECT: NOT MOVING METERS
Total Outstanding Inspections - 1
| Last Inspection Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/14/2006 | ELECTRIC - RECONNECT | N/A | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. THERE ARE 3 UNITS AT THIS ADDRESS, 3 METERS FOR ELECTRIC, LABEL ALL UNITS, METERS, DISCONNECTS, PANELS 2. COVERS MISSING TO MAIN BREAKERS AT SERVICE, THE WEATHER HAS DETERIORATED THE LABELING ON THE BREAKERS CAN'T READ INFO, OR BREAKER SIZE. REPAIR COVERS. 3. OPEN SPLICES MUST BE IN APPROVED J-BOX 4. GROUNDED OUTLETS, TWO WIRE CIRCUITS, CHANGE OUTLETS TO NON-GROUNDED TYPE OR GROUND CIRCUIT. 5. SMOKE DETECTORS REQUIRED IN SLEEPING AREAS. 6. HEATING & COOLING MUST BE INTACT & OPERABLE. 7. ONLY ONE 20 AMP. CIRCUIT, NOT ENOUGH FOR THIS SIZE OF HOUSE OBTAIN PROPER PERMITS FOR WORK TO BE DONE. PLAN MAY BE REQUIRED. |