Inspection History Details
Inspection Status: Denied
Inspection History: ELECTRIC - RECONNECT
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/14/2006 | ELECTRIC - RECONNECT | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. THERE ARE 3 UNITS AT THIS ADDRESS, 3 METERS FOR ELECTRIC, LABEL ALL UNITS, METERS, DISCONNECTS, PANELS 2. COVERS MISSING TO MAIN BREAKERS AT SERVICE, THE WEATHER HAS DETERIORATED THE LABELING ON THE BREAKERS CAN'T READ INFO, OR BREAKER SIZE. REPAIR COVERS. 3. OPEN SPLICES MUST BE IN APPROVED J-BOX 4. GROUNDED OUTLETS, TWO WIRE CIRCUITS, CHANGE OUTLETS TO NON-GROUNDED TYPE OR GROUND CIRCUIT. 5. SMOKE DETECTORS REQUIRED IN SLEEPING AREAS. 6. HEATING & COOLING MUST BE INTACT & OPERABLE. 7. ONLY ONE 20 AMP. CIRCUIT, NOT ENOUGH FOR THIS SIZE OF HOUSE OBTAIN PROPER PERMITS FOR WORK TO BE DONE. PLAN MAY BE REQUIRED. |