Permit: T06EL02156
Permit Details
Apply Date:
10/30/2006
Applicant:
RAM ELECTRIC INC
Description:
UPGRADE:ELECTRIC TO 200 AMP - DUPLEX
Contractors:
- RAM ELECTRIC INC
Outstanding Activity Conditions
Permit Number - T06EL02156
Permit Status: Final
Permit Description: UPGRADE:ELECTRIC TO 200 AMP - DUPLEX
Total Outstanding Activity Conditions - 1
| Date | Name |
|---|---|
| 10/30/2006 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Completed Inspections
Permit Status: Final
Permit Number: T06EL02156
Permit Description: UPGRADE:ELECTRIC TO 200 AMP - DUPLEX
Total Completed Inspections - 6
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/02/2006 | ELECTRIC - FINAL | CCLEMENS | Approved | IVRS - Inspection : The service is not per code.| 210* 1) MAST NEEDS TO BE BONDED-NEC 250.92 A,B 2) BURY G.E.C./BOND CONDUCTOR MINIMUM 12" OR SECURE TO STRUCTURE-NEC 250.64 B 3) BOND EACH UNITS WATER PIPE IF NOT COMMON-NEC 250.104 4) NEUTRAL TO FEEDERS TO BE INSULATED AND PROPERLY IDENTIFIED NEC 200 5) DO NOT USE NEUTRAL TO GROUND LOAD SIDE EQUIPMENT NEC250.24A5 6) USE EQUIPMENT GROUND FOR FEEDER J-BOXES NEC 250.148 7) CAN'T REMOVE J-BOX COVER FOR UNIT #2 NEC 110 8) PROPERLY RECONNECT PHONE AND CATV GROUNDS-NEC 800, 250 |
| 03/15/2010 | ELECTRIC - INTERMEDIATE | DSANTACR | Approved | |
| 03/15/2010 | ELECTRIC - UNDERGROUND | DSANTACR | Approved | |
| 03/15/2010 | ELECTRIC - SERVICE UPGRADE | DSANTACR | Approved | IVRS - Inspection :* |
| 03/16/2010 | TEP CLEARANCE - AM | JWEATHER | Approved | INCR CLEARED FOR #1 & 2 PER D. SANTACRUZ |
| 03/16/2010 | PERMIT FINALED | JWEATHER | Approved |