Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/15/2010 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 11/02/2006 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The service is not per code.| 210* 1) MAST NEEDS TO BE BONDED-NEC 250.92 A,B 2) BURY G.E.C./BOND CONDUCTOR MINIMUM 12" OR SECURE TO STRUCTURE-NEC 250.64 B 3) BOND EACH UNITS WATER PIPE IF NOT COMMON-NEC 250.104 4) NEUTRAL TO FEEDERS TO BE INSULATED AND PROPERLY IDENTIFIED NEC 200 5) DO NOT USE NEUTRAL TO GROUND LOAD SIDE EQUIPMENT NEC250.24A5 6) USE EQUIPMENT GROUND FOR FEEDER J-BOXES NEC 250.148 7) CAN'T REMOVE J-BOX COVER FOR UNIT #2 NEC 110 8) PROPERLY RECONNECT PHONE AND CATV GROUNDS-NEC 800, 250 |