Permit: T06EL02156

Parcel: 124080380


Addresses:

1527 E 8TH ST #01

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
03/15/2010 ELECTRIC - FINAL Approved IVRS - Inspection :*
11/02/2006 ELECTRIC - FINAL Denied IVRS - Inspection :
The service is not per code.| 210*
1) MAST NEEDS TO BE BONDED-NEC 250.92 A,B
2) BURY G.E.C./BOND CONDUCTOR MINIMUM 12" OR SECURE TO STRUCTURE-NEC 250.64 B
3) BOND EACH UNITS WATER PIPE IF NOT COMMON-NEC 250.104
4) NEUTRAL TO FEEDERS TO BE INSULATED AND PROPERLY IDENTIFIED NEC 200
5) DO NOT USE NEUTRAL TO GROUND LOAD SIDE EQUIPMENT NEC250.24A5
6) USE EQUIPMENT GROUND FOR FEEDER J-BOXES NEC 250.148
7) CAN'T REMOVE J-BOX COVER FOR UNIT #2 NEC 110
8) PROPERLY RECONNECT PHONE AND CATV GROUNDS-NEC 800, 250