Permit: T06EL01786
Permit Details
Apply Date:
09/01/2006
Applicant:
VERONICA HEWITT
Description:
ELEC UPGRADE 200AMPS
Outstanding Activity Conditions
Permit Number - T06EL01786
Permit Status: Expired
Permit Description: ELEC UPGRADE 200AMPS
Total Outstanding Activity Conditions - 1
| Date | Name |
|---|---|
| 09/01/2006 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Outstanding Inspections
Permit Status: Expired
Permit Number: T06EL01786
Permite Description: ELEC UPGRADE 200AMPS
Total Outstanding Inspections - 4
| Last Inspection Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/19/2006 | ELECTRIC - UNDERGROUND | N/A | Not ready for Inspection | IVRS - Inspection :* |
| 09/19/2006 | ELECTRIC - INTERMEDIATE | N/A | Not ready for Inspection | IVRS - Inspection :* |
| 09/19/2006 | ELECTRIC - SERVICE UPGRADE | N/A | Not ready for Inspection | IVRS - Inspection :* |
| 09/22/2006 | ELECTRIC - FINAL | N/A | Denied | IVRS - Inspection : The service is not per code.| 210* 1. SPACE IN FRONT OF SERVICE IS OBSTRUCTED BY PLANTER NEC 110.26 2. NEED LISTED GUY KIT OR STIFF ARM TO BRACE MAST NEC 230.28 3. SELF TAP SCREW NOT ALLOWED FOR J-BOX GROUND LUG NEC 110, 250 AND REMOVE PAINT UNDER LUG - NEC 250.12 4. SEAL UNUSED BREAKER OPENING - NEC 110.12 5. IDENTIFY PANEL DIRECTORY -- NEC 408.4 6. TIGHTEN ALL BOND CLAMPS - NEC 110 7. BOND EXISTING UFER TO SERVICE -- NEC 250.50 8. COMPLETE RACEWAY FOR BRANCH CKT RIGHT OF SERVICE & INSTALL J-BOX COVER SCREW. |