Inspection History Details
Inspection Status: Denied
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/22/2006 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The service is not per code.| 210* 1. SPACE IN FRONT OF SERVICE IS OBSTRUCTED BY PLANTER NEC 110.26 2. NEED LISTED GUY KIT OR STIFF ARM TO BRACE MAST NEC 230.28 3. SELF TAP SCREW NOT ALLOWED FOR J-BOX GROUND LUG NEC 110, 250 AND REMOVE PAINT UNDER LUG - NEC 250.12 4. SEAL UNUSED BREAKER OPENING - NEC 110.12 5. IDENTIFY PANEL DIRECTORY -- NEC 408.4 6. TIGHTEN ALL BOND CLAMPS - NEC 110 7. BOND EXISTING UFER TO SERVICE -- NEC 250.50 8. COMPLETE RACEWAY FOR BRANCH CKT RIGHT OF SERVICE & INSTALL J-BOX COVER SCREW. |
|
| 09/19/2006 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* CALL WHEN READY |