Permit: T06EL01786

Parcel: 115172320


Addresses:

1310 N GILA ST

Inspection Status: Denied

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
09/22/2006 ELECTRIC - FINAL Denied IVRS - Inspection :
The service is not per code.| 210*
1. SPACE IN FRONT OF SERVICE IS OBSTRUCTED BY PLANTER
NEC 110.26
2. NEED LISTED GUY KIT OR STIFF ARM TO BRACE MAST
NEC 230.28
3. SELF TAP SCREW NOT ALLOWED FOR J-BOX GROUND LUG
NEC 110, 250 AND REMOVE PAINT UNDER LUG - NEC 250.12
4. SEAL UNUSED BREAKER OPENING - NEC 110.12
5. IDENTIFY PANEL DIRECTORY -- NEC 408.4
6. TIGHTEN ALL BOND CLAMPS - NEC 110
7. BOND EXISTING UFER TO SERVICE -- NEC 250.50
8. COMPLETE RACEWAY FOR BRANCH CKT RIGHT OF
SERVICE & INSTALL J-BOX COVER SCREW.
09/19/2006 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
CALL WHEN READY