Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit: T06EL01773
Permit Details
Apply Date:
08/31/2006
Applicant:
CASCADE ELECTRIC INC *C
Description:
REPAIR: METER BASE (APA)
Contractors:
- CASCADE ELECTRIC INC *C
Outstanding Activity Conditions
Permit Number - T06EL01773
Permit Status: Withdrwn
Permit Description: REPAIR: METER BASE (APA)
Total Outstanding Activity Conditions - 1
Date | Name |
---|---|
08/31/2006 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Outstanding Inspections
Permit Status: Withdrwn
Permit Number: T06EL01773
Permite Description: REPAIR: METER BASE (APA)
Total Outstanding Inspections - 1
Last Inspection Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
02/28/2007 | ELECTRIC - FINAL | N/A | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. DO NOT USE BROWN, ORANGE OR YELLOW COLORS IF YOU DO TAPE THEM WITH PROPER COLORS FOR VOLTAGE. 2. IF WHITE IS USED AS HOT TAPE ENTIRE LENGTH SHOWN IN GUTTER OR DISCONNECTS 3. ALL DISCONNECTS SHOWN ARE MISSING A CIRCUIT BREAKER COVER 4. MOST OFFSET NIPPLES AT BOTTOM OF METERS ARE NOT MAKING CONTACT OR SET RIGHT 5. UFER NOT TIED TO NEUTRAL TO BE DONE AT TOP GUTTER 6. OFFSET NIPPLES NOT ALL MAKING CONTACT AT BOTTOM OF DISCONNECT. 7. OFFSET NIPPLES ENTERING BOTTOM OF METER ENCLOSURES TO HAVE GROUND BUSHING BECAUSE THEY CARRY UNPROTECTED CONDUCTORS AND GO THRU CONCENTRICS. |