Inspection History Details
Inspection Status: Denied
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/28/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. DO NOT USE BROWN, ORANGE OR YELLOW COLORS IF YOU DO TAPE THEM WITH PROPER COLORS FOR VOLTAGE. 2. IF WHITE IS USED AS HOT TAPE ENTIRE LENGTH SHOWN IN GUTTER OR DISCONNECTS 3. ALL DISCONNECTS SHOWN ARE MISSING A CIRCUIT BREAKER COVER 4. MOST OFFSET NIPPLES AT BOTTOM OF METERS ARE NOT MAKING CONTACT OR SET RIGHT 5. UFER NOT TIED TO NEUTRAL TO BE DONE AT TOP GUTTER 6. OFFSET NIPPLES NOT ALL MAKING CONTACT AT BOTTOM OF DISCONNECT. 7. OFFSET NIPPLES ENTERING BOTTOM OF METER ENCLOSURES TO HAVE GROUND BUSHING BECAUSE THEY CARRY UNPROTECTED CONDUCTORS AND GO THRU CONCENTRICS. |