Permit Details

Status:
Expired
Type:
SINGLE FAMILY OTHER
Address NEW:
842 W CALLE COLADO
Apply Date:
08/25/2006
Applicant:
MUNOZ JOSE R
Description:
REPAIRS:STORM DAMAGE - ELECT

Permit Reviews

Permit Number - T06EL01722
Permit Status: Expired
Permit Description: REPAIRS:STORM DAMAGE - ELECT
Start Date Submittal Complete Date Status  
08/25/2006 ELECTRICAL 08/25/2006 COMPLETED Review Details

Outstanding Activity Conditions

Permit Number - T06EL01722
Permit Status: Expired
Permit Description: REPAIRS:STORM DAMAGE - ELECT
Total Outstanding Activity Conditions - 1
Date Name
08/25/2006 PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION.

Outstanding Inspections

Permit Status: Expired
Permit Number: T06EL01722
Permite Description: REPAIRS:STORM DAMAGE - ELECT
Total Outstanding Inspections - 4
Last Inspection Date Description Inspector Results Comments
08/29/2006 ELECTRIC - UNDERGROUND N/A Denied IVRS - Inspection :
See detailed listing on site.| 999*
08/29/2006 ELECTRIC - INTERMEDIATE N/A Denied IVRS - Inspection :
See detailed listing on site.| 999*
08/29/2006 ELECTRIC - CABLE DROP N/A Denied IVRS - Inspection :
See detailed listing on site.| 999*
08/29/2006 ELECTRIC - FINAL N/A Denied IVRS - Inspection :
See detailed listing on site.| 999*
NOTES
1. NEW SERVICE PANEL TO HIGH, 6'7" MAX ALLOWABLE ABOVE GRADE TO HIGHEST CIRCUIT BREAKER.
2. SUPPORT RISER CONDUIT UNDER ROOF OVERHANG.
3. INSTALL 2 GROUND RODS 6' MIN. APART & BOND GAS PIPING ALSO
4. SPLIT UP LOADS WHEN USING TWIN BREAKERS, IF NOT YOU MUST RUN A SEPARATE NEUTRAL FOR EACH CIRCUIT.