Inspection History Details
Inspection Status: Denied
Inspection History: ELECTRIC - FINAL
Permit Number - T06EL01722
Inspection Description - ELECTRIC - FINAL
Inspection Status - Denied
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/29/2006 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* NOTES 1. NEW SERVICE PANEL TO HIGH, 6'7" MAX ALLOWABLE ABOVE GRADE TO HIGHEST CIRCUIT BREAKER. 2. SUPPORT RISER CONDUIT UNDER ROOF OVERHANG. 3. INSTALL 2 GROUND RODS 6' MIN. APART & BOND GAS PIPING ALSO 4. SPLIT UP LOADS WHEN USING TWIN BREAKERS, IF NOT YOU MUST RUN A SEPARATE NEUTRAL FOR EACH CIRCUIT. |