Permit: T06EL01687
Permit Details
Apply Date:
08/23/2006
Applicant:
MEHL SANDRA
Description:
change out panel
Contractors:
- MEHL ELECTRIC SERVICE INC,*C
Outstanding Activity Conditions
Permit Number - T06EL01687
Permit Status: Final
Permit Description: change out panel
Total Outstanding Activity Conditions - 1
| Date | Name |
|---|---|
| 08/23/2006 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Completed Inspections
Permit Status: Final
Permit Number: T06EL01687
Permit Description: change out panel
Total Completed Inspections - 6
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/30/2006 | ELECTRIC - FINAL | RHOLLAND | Approved | IVRS - Inspection : See detailed listing on site.| 999* 1. BOND GAG TO INTERIOR SIDE OF VALUE 2. SUPPORT CONDUIT ON SIDE OF PANEL AND ABOVE PANEL 3' 3. A PERMANENT METAL ADDRESS LABEL IS NEEDED 4. LABEL BREAKERS 5. A BOND BUSHING IS NEEDED FOR SERVICE NIPPLE 6. PROTECT CABLES ENTERING BACK OF PANEL 7. TIGHTEN LOOSE FITTINGS 8. FILL USUSED PORTION OF OPENINGS 9. ANTI-OXIDE COMPOUND FOR ALL ALUMINUM CONDUCTORS 10. DO NOT SPLIT OR FORK STRANDED CONDUCTORS. |
| 01/09/2007 | ELECTRIC - INTERMEDIATE | RHOLLAND | Approved | |
| 01/09/2007 | ELECTRIC - UNDERGROUND | RHOLLAND | Approved | |
| 01/09/2007 | ELECTRIC - RECONNECT | RHOLLAND | Approved | |
| 01/10/2007 | PERMIT FINALED | JWEATHER | Approved | |
| 01/10/2007 | TEP CLEARANCE - AM | JWEATHER | Approved | INCR CLEARED PER R. HOLLANDER |