Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/09/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 08/30/2006 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. BOND GAG TO INTERIOR SIDE OF VALUE 2. SUPPORT CONDUIT ON SIDE OF PANEL AND ABOVE PANEL 3' 3. A PERMANENT METAL ADDRESS LABEL IS NEEDED 4. LABEL BREAKERS 5. A BOND BUSHING IS NEEDED FOR SERVICE NIPPLE 6. PROTECT CABLES ENTERING BACK OF PANEL 7. TIGHTEN LOOSE FITTINGS 8. FILL USUSED PORTION OF OPENINGS 9. ANTI-OXIDE COMPOUND FOR ALL ALUMINUM CONDUCTORS 10. DO NOT SPLIT OR FORK STRANDED CONDUCTORS. |