Permit: T06EL01687

Parcel: 11002001H


Addresses:

4250 E RIVER RD

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
01/09/2007 ELECTRIC - FINAL Approved IVRS - Inspection :*
08/30/2006 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. BOND GAG TO INTERIOR SIDE OF VALUE
2. SUPPORT CONDUIT ON SIDE OF PANEL AND ABOVE PANEL 3'
3. A PERMANENT METAL ADDRESS LABEL IS NEEDED
4. LABEL BREAKERS
5. A BOND BUSHING IS NEEDED FOR SERVICE NIPPLE
6. PROTECT CABLES ENTERING BACK OF PANEL
7. TIGHTEN LOOSE FITTINGS
8. FILL USUSED PORTION OF OPENINGS
9. ANTI-OXIDE COMPOUND FOR ALL ALUMINUM CONDUCTORS
10. DO NOT SPLIT OR FORK STRANDED CONDUCTORS.