Status:
Final
Type:
SINGLE FAMILY OTHER
Address:
8247 E BRENT PL
Address NEW:
8247 E BRENT PL
Apply Date:
08/10/2006
Applicant:
RAY'S ELECTRIC ,
Description:
ELEC UPGRADE 200AMPS
Contractors:
  • RAY'S ELECTRIC ,

Outstanding Activity Conditions

Permit Number - T06EL01586
Permit Status: Final
Permit Description: ELEC UPGRADE 200AMPS
Total Outstanding Activity Conditions - 1
Date Name
08/10/2006 PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION.

Completed Inspections

Permit Status: Final
Permit Number: T06EL01586
Permit Description: ELEC UPGRADE 200AMPS
Total Completed Inspections - 6
Date Description Inspector Results Comments
12/05/2006 ELECTRIC - FINAL RHOLLAND Approved IVRS - Inspection :*
1. WHERE IS OTHER GROUND ROD?
2. CANNOT PASS THROUGH UPPER SECTION OF PANEL PER MANUFACTURERS LABEL.
3. SEAL ENTRANCES ABOVE CURRENT CARRING PARTS.
4. CORD NOT ALLOWED FOR PERMANENT WIRING
METHOD 400.7 & 8
5. RECEPTACLE COVER TO BE WEATHERPROOF WHETHER OR NOT PLUGGED INTO 406.8
6. SECURE CABLES TO BACK OF JUNCTION BOX
7. BOND JUNCTION BOX
8. CANNOT CONNECT GROUNDED CONDUCTOR TO GROUNDING CONDUCTOR.
9. PLEASE PROVIDE RIDGID GUY BACK BRACE SUPPORT FOR RISER.
10. VERIFY NEW PERMIT FOR NEW A/C UNIT & MAINTAIN WORKING CLEARANCES AT DISCONNECT.
12/05/2006 ELECTRIC - SERVICE UPGRADE RHOLLAND Approved IVRS - Inspection :*
03/16/2007 ELECTRIC - INTERMEDIATE RHOLLAND Approved
03/16/2007 ELECTRIC - UNDERGROUND RHOLLAND Approved
03/19/2007 PERMIT FINALED JWEATHER Approved
03/19/2007 TEP CLEARANCE - AM JWEATHER Approved INCR CLEARED PER R. HOLLANDER