Permit: T06EL01586
Permit Details
Apply Date:
08/10/2006
Applicant:
RAY'S ELECTRIC ,
Description:
ELEC UPGRADE 200AMPS
Contractors:
- RAY'S ELECTRIC ,
Outstanding Activity Conditions
Permit Number - T06EL01586
Permit Status: Final
Permit Description: ELEC UPGRADE 200AMPS
Total Outstanding Activity Conditions - 1
| Date | Name |
|---|---|
| 08/10/2006 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Completed Inspections
Permit Status: Final
Permit Number: T06EL01586
Permit Description: ELEC UPGRADE 200AMPS
Total Completed Inspections - 6
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/05/2006 | ELECTRIC - FINAL | RHOLLAND | Approved | IVRS - Inspection :* 1. WHERE IS OTHER GROUND ROD? 2. CANNOT PASS THROUGH UPPER SECTION OF PANEL PER MANUFACTURERS LABEL. 3. SEAL ENTRANCES ABOVE CURRENT CARRING PARTS. 4. CORD NOT ALLOWED FOR PERMANENT WIRING METHOD 400.7 & 8 5. RECEPTACLE COVER TO BE WEATHERPROOF WHETHER OR NOT PLUGGED INTO 406.8 6. SECURE CABLES TO BACK OF JUNCTION BOX 7. BOND JUNCTION BOX 8. CANNOT CONNECT GROUNDED CONDUCTOR TO GROUNDING CONDUCTOR. 9. PLEASE PROVIDE RIDGID GUY BACK BRACE SUPPORT FOR RISER. 10. VERIFY NEW PERMIT FOR NEW A/C UNIT & MAINTAIN WORKING CLEARANCES AT DISCONNECT. |
| 12/05/2006 | ELECTRIC - SERVICE UPGRADE | RHOLLAND | Approved | IVRS - Inspection :* |
| 03/16/2007 | ELECTRIC - INTERMEDIATE | RHOLLAND | Approved | |
| 03/16/2007 | ELECTRIC - UNDERGROUND | RHOLLAND | Approved | |
| 03/19/2007 | PERMIT FINALED | JWEATHER | Approved | |
| 03/19/2007 | TEP CLEARANCE - AM | JWEATHER | Approved | INCR CLEARED PER R. HOLLANDER |