Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/16/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 12/05/2006 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. WHERE IS OTHER GROUND ROD? 2. CANNOT PASS THROUGH UPPER SECTION OF PANEL PER MANUFACTURERS LABEL. 3. SEAL ENTRANCES ABOVE CURRENT CARRING PARTS. 4. CORD NOT ALLOWED FOR PERMANENT WIRING METHOD 400.7 & 8 5. RECEPTACLE COVER TO BE WEATHERPROOF WHETHER OR NOT PLUGGED INTO 406.8 6. SECURE CABLES TO BACK OF JUNCTION BOX 7. BOND JUNCTION BOX 8. CANNOT CONNECT GROUNDED CONDUCTOR TO GROUNDING CONDUCTOR. 9. PLEASE PROVIDE RIDGID GUY BACK BRACE SUPPORT FOR RISER. 10. VERIFY NEW PERMIT FOR NEW A/C UNIT & MAINTAIN WORKING CLEARANCES AT DISCONNECT. |