Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit: T06EL01371
Permit Details
Apply Date:
07/19/2006
Applicant:
MEHL ELECTRIC SERVICE INC,*C
Description:
ELECTRIC UPGRADE 400 AMP
Contractors:
- MEHL ELECTRIC SERVICE INC,*C
Permit Reviews
Permit Number - T06EL01371
Permit Status: Closed
Permit Description: ELECTRIC UPGRADE 400 AMP
Start Date | Submittal | Complete Date | Status |
---|---|---|---|
08/01/2006 | ELECTRICAL | 08/01/2006 | COMPLETED |
Outstanding Activity Conditions
Permit Number - T06EL01371
Permit Status: Closed
Permit Description: ELECTRIC UPGRADE 400 AMP
Total Outstanding Activity Conditions - 1
Date | Name |
---|---|
07/19/2006 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Outstanding Inspections
Permit Status: Closed
Permit Number: T06EL01371
Permite Description: ELECTRIC UPGRADE 400 AMP
Total Outstanding Inspections - 2
Last Inspection Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/02/2006 | ELECTRIC - INTERMEDIATE | N/A | Partial Approval | OK TO CLEAR TO TEP M1, M2 AND M3 |
10/08/2007 | ELECTRIC - SERVICE UPGRADE | N/A | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. NEED MINIMUM #3 EQUIPMENT GROUND FOR 400AMP CKT NEC 250.122 2. NEUTRALS & GROUNDS TO BE SEPARATED IN PANELS "A" "B" "C" - NEC 250.32 3. FINISH ALL WIRING PER PLAN |
Completed Inspections
Permit Status: Closed
Permit Number: T06EL01371
Permit Description: ELECTRIC UPGRADE 400 AMP
Total Completed Inspections - 1
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/02/2006 | TEP CLEARANCE - PM | RSCHULER | Approved | OK TO CLEAR - PER RANDY SCHULER - CLEARANCE SENT |