Permit: T06EL01371

Parcel: 106090110


Addresses:

1635 W ROGER RD 1M


Inspection Status: Denied

Inspection History: ELECTRIC - SERVICE UPGRADE

Permit Number - T06EL01371

Inspection Description - ELECTRIC - SERVICE UPGRADE

Inspection Status - Denied

Date Description Inspector Results Comments
10/08/2007 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. NEED MINIMUM #3 EQUIPMENT GROUND FOR 400AMP CKT
NEC 250.122
2. NEUTRALS & GROUNDS TO BE SEPARATED IN PANELS
"A" "B" "C" - NEC 250.32
3. FINISH ALL WIRING PER PLAN
08/14/2007 ELECTRIC - SERVICE UPGRADE Not ready for Inspection IVRS - Inspection :*
REVISE PLANS TO SHOW ACTUAL SCOPE OF WORK THEN CALL FOR INSPECTION
08/06/2007 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection :
NEED PLANS AND ELECTRICIAN ON SITE FOR INSPECTION
08/02/2007 ELECTRIC - SERVICE UPGRADE Not ready for Inspection IVRS - Inspection :*
08/03/2006 ELECTRIC - SERVICE UPGRADE Partial Approval 1) Install bonding bushings on the nipple between the service and meter. Typical for M1, M2, M3. DONE 8/04/06
2) Install a 1/0 grding elec conductor per plans.Typical of M1,M2, M3 DONE 08/04/06
3) Address the services. Typical of M1,M2, M3. DONE 08/08/06
4) Panel B requires MB.
5) Plan indicates the main fuses for disconnects M1,M2, M3 should be LPNRK, FRNR fuses are installed.