Permit: T06EL01289
Permit Details
Apply Date:
07/10/2006
Applicant:
CARHUFF, PHILIP ANDREW
Description:
SERVICE:ELECTRIC:SITE LIGHTING
Architects:
- CARHUFF, PHILIP ANDREW
Outstanding Activity Conditions
Permit Number - T06EL01289
Permit Status: Expired
Permit Description: SERVICE:ELECTRIC:SITE LIGHTING
Total Outstanding Activity Conditions - 1
| Date | Name |
|---|---|
| 07/10/2006 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Outstanding Inspections
Permit Status: Expired
Permit Number: T06EL01289
Permite Description: SERVICE:ELECTRIC:SITE LIGHTING
Total Outstanding Inspections - 1
| Last Inspection Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| BUILDING - FINAL | N/A | Not Inspected |
Completed Inspections
Permit Status: Expired
Permit Number: T06EL01289
Permit Description: SERVICE:ELECTRIC:SITE LIGHTING
Total Completed Inspections - 9
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/26/2006 | EXCAVATION/LAYOUT REBAR & ZON | GDABBS | Approved | IVRS - Inspection :* |
| 08/24/2006 | ELECTRIC - INTERMEDIATE | RMAJUTA | Approved | IVRS - Inspection :* 1. PROVIDE LETTER AS REQUESTED ON LAST INSPECTION. 2. WATER HOSE BIB CANNOT BE IN FRONT OF SERVICE CLEARANCE REQUIRED AS PER NEC 2002 110-26 3. MAIN BREAKER IN PANEL MUST HAVE A TIE DOWN AS PER 408.16 F 4. ID PANEL SCHEDULE 5. SCRAPE PAINT BEHIND GROUND LUG IN J-BOX 6. REMOVE DOUBLE LUGGING OF SOLID & STRANDED WIRES AT CONTACTOR, ALSO FEED OF #12 SOLID WIRE CANNOT GO INTO 3 PHASE BREAKER. 7. GROUND TIME CLOUD 8. OUTSIDE LIGHT TO BE INSTALLED. |
| 09/15/2006 | OUTDOOR LIGHTING FINAL | RMAJUTA | Approved | |
| 09/15/2006 | ELECTRIC - OUTDOOR LIGHTING | RMAJUTA | Approved | |
| 09/15/2006 | ELECTRIC - CABLE DROP | RMAJUTA | Approved | |
| 09/18/2006 | TEP CLEARANCE - AM | JWEATHER | Approved | ECO CLEARED PER R. MAJUTA |
| 09/18/2006 | ELECTRIC - UNDERGROUND | RMAJUTA | Approved | IVRS - Inspection :* |
| 09/18/2006 | ELECTRIC - UFER | RMAJUTA | Approved | IVRS - Inspection :* |
| 09/18/2006 | ELECTRIC - FINAL | RMAJUTA | Approved | IVRS - Inspection :* |