Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/24/2006 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* 1. PROVIDE LETTER AS REQUESTED ON LAST INSPECTION. 2. WATER HOSE BIB CANNOT BE IN FRONT OF SERVICE CLEARANCE REQUIRED AS PER NEC 2002 110-26 3. MAIN BREAKER IN PANEL MUST HAVE A TIE DOWN AS PER 408.16 F 4. ID PANEL SCHEDULE 5. SCRAPE PAINT BEHIND GROUND LUG IN J-BOX 6. REMOVE DOUBLE LUGGING OF SOLID & STRANDED WIRES AT CONTACTOR, ALSO FEED OF #12 SOLID WIRE CANNOT GO INTO 3 PHASE BREAKER. 7. GROUND TIME CLOUD 8. OUTSIDE LIGHT TO BE INSTALLED. |