Permit Details

Status:
Closed
Type:
SINGLE FAMILY OTHER
Apply Date:
07/03/2006
Applicant:
ROBERT THUNHILL
Description:
ELEC RECONNECT

Outstanding Activity Conditions

Permit Number - T06EL01260
Permit Status: Closed
Permit Description: ELEC RECONNECT
Total Outstanding Activity Conditions - 1
Date Name
07/03/2006 PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION.

Outstanding Inspections

Permit Status: Closed
Permit Number: T06EL01260
Permite Description: ELEC RECONNECT
Total Outstanding Inspections - 2
Last Inspection Date Description Inspector Results Comments
07/12/2006 ELECTRIC - RECONNECT N/A Denied IVRS - Inspection :
See detailed listing on site.| 999*
07/12/2006 ELECTRIC - FINAL N/A Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. CORD OUTSIDE IS #10 30 AMP. WIRE WHICH GO INTO TRAILER WITH #12 20 AMP. WIRE.
2. OPEN SPLICES NOT ALLOWED (NEXT TO BED INSIDE MUST BE IN A SUPPORTED J-BOX)
3. WORKING SMOKE DETECTOR
4. INSIDE BREAKER BOX, NEUTRALS TO BE SPLICED BY OTHER THAN TWISTING AND TAPE, ALSO REMOVE ZIP CORD STICKING OUT OF SPLICE.