Permit: T06EL01260
Permit Details
Apply Date:
07/03/2006
Applicant:
ROBERT THUNHILL
Description:
ELEC RECONNECT
Outstanding Activity Conditions
Permit Number - T06EL01260
Permit Status: Closed
Permit Description: ELEC RECONNECT
Total Outstanding Activity Conditions - 1
Date | Name |
---|---|
07/03/2006 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Outstanding Inspections
Permit Status: Closed
Permit Number: T06EL01260
Permite Description: ELEC RECONNECT
Total Outstanding Inspections - 2
Last Inspection Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
07/12/2006 | ELECTRIC - RECONNECT | N/A | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
07/12/2006 | ELECTRIC - FINAL | N/A | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. CORD OUTSIDE IS #10 30 AMP. WIRE WHICH GO INTO TRAILER WITH #12 20 AMP. WIRE. 2. OPEN SPLICES NOT ALLOWED (NEXT TO BED INSIDE MUST BE IN A SUPPORTED J-BOX) 3. WORKING SMOKE DETECTOR 4. INSIDE BREAKER BOX, NEUTRALS TO BE SPLICED BY OTHER THAN TWISTING AND TAPE, ALSO REMOVE ZIP CORD STICKING OUT OF SPLICE. |