Inspection History Details
Inspection Status: Denied
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/12/2006 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. CORD OUTSIDE IS #10 30 AMP. WIRE WHICH GO INTO TRAILER WITH #12 20 AMP. WIRE. 2. OPEN SPLICES NOT ALLOWED (NEXT TO BED INSIDE MUST BE IN A SUPPORTED J-BOX) 3. WORKING SMOKE DETECTOR 4. INSIDE BREAKER BOX, NEUTRALS TO BE SPLICED BY OTHER THAN TWISTING AND TAPE, ALSO REMOVE ZIP CORD STICKING OUT OF SPLICE. |