Permit: T06EL00879
Permit Details
Apply Date:
05/10/2006
Applicant:
DAMITIO CONSTRUCTION INC ,
Description:
UPGR: 200 AMP SRVC OVERHEAD TO UNDRGRND
Contractors:
- DAMITIO CONSTRUCTION INC ,
Outstanding Activity Conditions
Permit Number - T06EL00879
Permit Status: Final
Permit Description: UPGR: 200 AMP SRVC OVERHEAD TO UNDRGRND
Total Outstanding Activity Conditions - 1
Date | Name |
---|---|
05/10/2006 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Completed Inspections
Permit Status: Final
Permit Number: T06EL00879
Permit Description: UPGR: 200 AMP SRVC OVERHEAD TO UNDRGRND
Total Completed Inspections - 4
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/23/2006 | ELECTRIC - UNDERGROUND | RMAJUTA | Approved | IVRS - Inspection :* 1. OK 2 1/2" PVC SERVICE TO POLE 2. 2-GRD RODS W/#4 COPPER TO SERVICE. |
06/05/2006 | TEP CLEARANCE - AM | JWEATHER | Approved | INCR CLEARED PER C. CLEMENS |
09/18/2007 | ELECTRIC - FINAL | CCLEMENS | Approved | IVRS - Inspection : See detailed listing on site.| 999* 1. SERVICE DOOR DOES NOT CLOSE PROPERLY 2. NEED AN EQUIPMENT GROUND TO OLD J-BOX DISCONNECT, NEUTRALS AND GROUNDS TO BE SEPARATED (PROVIDE LADDER FOR INSPECTION) 3. CORRECTLY IDENTIFY PANEL DIRECTORY - DON'T ABBREVIATE 4. J-BOX UNDER PANEL IS OVERFILLED AND NEEDS MINIMUM #12 CU GROUND TO BOX PARTIAL INSPECTION - PROVIDE INTERIOR ACCESS |
02/08/2008 | PERMIT FINALED | BFLORES | Approved |