Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Details

Status:
Final
Type:
COMMERCIAL OTHER
Apply Date:
05/10/2006
Applicant:
DAMITIO CONSTRUCTION INC ,
Description:
UPGR: 200 AMP SRVC OVERHEAD TO UNDRGRND
Contractors:
  • DAMITIO CONSTRUCTION INC ,

Outstanding Activity Conditions

Permit Number - T06EL00879
Permit Status: Final
Permit Description: UPGR: 200 AMP SRVC OVERHEAD TO UNDRGRND
Total Outstanding Activity Conditions - 1
Date Name
05/10/2006 PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION.

Completed Inspections

Permit Status: Final
Permit Number: T06EL00879
Permit Description: UPGR: 200 AMP SRVC OVERHEAD TO UNDRGRND
Total Completed Inspections - 4
Date Description Inspector Results Comments
05/23/2006 ELECTRIC - UNDERGROUND RMAJUTA Approved IVRS - Inspection :*
1. OK 2 1/2" PVC SERVICE TO POLE
2. 2-GRD RODS W/#4 COPPER TO SERVICE.
06/05/2006 TEP CLEARANCE - AM JWEATHER Approved INCR CLEARED PER C. CLEMENS
09/18/2007 ELECTRIC - FINAL CCLEMENS Approved IVRS - Inspection :
See detailed listing on site.| 999*
1. SERVICE DOOR DOES NOT CLOSE PROPERLY
2. NEED AN EQUIPMENT GROUND TO OLD J-BOX DISCONNECT, NEUTRALS AND GROUNDS TO BE SEPARATED (PROVIDE LADDER FOR INSPECTION)
3. CORRECTLY IDENTIFY PANEL DIRECTORY -
DON'T ABBREVIATE
4. J-BOX UNDER PANEL IS OVERFILLED AND NEEDS MINIMUM #12 CU GROUND TO BOX

PARTIAL INSPECTION - PROVIDE INTERIOR ACCESS
02/08/2008 PERMIT FINALED BFLORES Approved