Permit: T06EL00879

Parcel: 12409158A


Addresses:

1809 E BROADWAY BL


Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T06EL00879

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
02/07/2008 ELECTRIC - FINAL Approved IVRS - Inspection :*
02/06/2008 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
WORK NOT COMPLETE

RENE 850-4632
02/05/2008 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
02/01/2008 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
CANCELED
01/31/2008 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. REMOVE TEMP POWER RECEPTACLE OR INSTALL AS PER CODES
2. #8 NM CABLE AMPACITY TO BE AS PER 334.80
3. INSTALL BOND LUG TO BUSHING
4. SECURE CABLES TO BOX 312.5(C)
5. FINISH PREVIOUS ITEM #1
6. WHERE ARE WATER & GAS BONDS
01/29/2008 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. IDENTIFY WHITE WIRE USED AS PHASE CONDUCTOR PROPERLY
2. INSTALL BREAKERS LISTED FOR USE IN SIEMENS PANEL
3. RECALL BOTH PERMITS @ SAME TIME WHEN READY FOR FINAL ON ACTIVITY T07CM03500
09/18/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. SERVICE DOOR DOES NOT CLOSE PROPERLY
2. NEED AN EQUIPMENT GROUND TO OLD J-BOX DISCONNECT, NEUTRALS AND GROUNDS TO BE SEPARATED (PROVIDE LADDER FOR INSPECTION)
3. CORRECTLY IDENTIFY PANEL DIRECTORY -
DON'T ABBREVIATE
4. J-BOX UNDER PANEL IS OVERFILLED AND NEEDS MINIMUM #12 CU GROUND TO BOX

PARTIAL INSPECTION - PROVIDE INTERIOR ACCESS
06/02/2006 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1) EXPOSE GROUND RODS
2) IDENTIFY PANEL DIRECTORY