Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Details

Status:
Expired
Type:
SINGLE FAMILY OTHER
Address:
5519 E 4TH ST
Address NEW:
5519 E 4TH ST
Apply Date:
04/13/2006
Applicant:
ZEIGLER PATRICIA A
Description:
ELEC: UPGRADE TO 200 AMP

Permit Reviews

Permit Number - T06EL00713
Permit Status: Expired
Permit Description: ELEC: UPGRADE TO 200 AMP
Start Date Submittal Complete Date Status  
04/13/2006 ELECTRICAL 04/13/2006 COMPLETED Review Details

Outstanding Activity Conditions

Permit Number - T06EL00713
Permit Status: Expired
Permit Description: ELEC: UPGRADE TO 200 AMP
Total Outstanding Activity Conditions - 1
Date Name
04/13/2006 PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION.

Outstanding Inspections

Permit Status: Expired
Permit Number: T06EL00713
Permite Description: ELEC: UPGRADE TO 200 AMP
Total Outstanding Inspections - 1
Last Inspection Date Description Inspector Results Comments
04/18/2007 ELECTRIC - SERVICE UPGRADE N/A Not ready for Inspection 1. PROPERLY IDENTIFY UNINSULATED NEUTRAL. THIS IS AN UNGROUNDED SYSTEM.
2. USE A SPLIT BOLT LISTED FOR COPPER AND ALUMINUM TERMINATIONS.
3. ALUMINUM CONDUCTORS TO USE ANTI-OXIDE COMPOUND
4. TIGHTEN LOOSE CONDUIT FITTINGS
5. BREAKER TO BE LISTED FOR USE BY MANUFACTURE
6. SUPPORT CONDUITS WITHIN 3' OF BOXES AND CONDUIT BODIES.
7. PLEASE VERIFY WATER BOND.

Documents

File Name Document Type  
None DOCUMENTS VIEW