Permit: T06EL00713
Permit Details
Apply Date:
04/13/2006
Applicant:
ZEIGLER PATRICIA A
Description:
ELEC: UPGRADE TO 200 AMP
Permit Reviews
Permit Number - T06EL00713
Permit Status: Expired
Permit Description: ELEC: UPGRADE TO 200 AMP
| Start Date | Submittal | Complete Date | Status |
|---|---|---|---|
| 04/13/2006 | ELECTRICAL | 04/13/2006 | COMPLETED |
Outstanding Activity Conditions
Permit Number - T06EL00713
Permit Status: Expired
Permit Description: ELEC: UPGRADE TO 200 AMP
Total Outstanding Activity Conditions - 1
| Date | Name |
|---|---|
| 04/13/2006 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Outstanding Inspections
Permit Status: Expired
Permit Number: T06EL00713
Permite Description: ELEC: UPGRADE TO 200 AMP
Total Outstanding Inspections - 1
| Last Inspection Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/18/2007 | ELECTRIC - SERVICE UPGRADE | N/A | Not ready for Inspection | 1. PROPERLY IDENTIFY UNINSULATED NEUTRAL. THIS IS AN UNGROUNDED SYSTEM. 2. USE A SPLIT BOLT LISTED FOR COPPER AND ALUMINUM TERMINATIONS. 3. ALUMINUM CONDUCTORS TO USE ANTI-OXIDE COMPOUND 4. TIGHTEN LOOSE CONDUIT FITTINGS 5. BREAKER TO BE LISTED FOR USE BY MANUFACTURE 6. SUPPORT CONDUITS WITHIN 3' OF BOXES AND CONDUIT BODIES. 7. PLEASE VERIFY WATER BOND. |