Inspection History Details
Inspection Status: Not ready for Inspection
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/18/2007 | ELECTRIC - SERVICE UPGRADE | Not ready for Inspection | 1. PROPERLY IDENTIFY UNINSULATED NEUTRAL. THIS IS AN UNGROUNDED SYSTEM. 2. USE A SPLIT BOLT LISTED FOR COPPER AND ALUMINUM TERMINATIONS. 3. ALUMINUM CONDUCTORS TO USE ANTI-OXIDE COMPOUND 4. TIGHTEN LOOSE CONDUIT FITTINGS 5. BREAKER TO BE LISTED FOR USE BY MANUFACTURE 6. SUPPORT CONDUITS WITHIN 3' OF BOXES AND CONDUIT BODIES. 7. PLEASE VERIFY WATER BOND. |