Permit: T06EL00641
Permit Details
Apply Date:
04/06/2006
Applicant:
PICCARRETA CARL A & GRACE R JT/RS
Description:
REPAIR: ELECTRIC SYSTEM
Permit Reviews
Permit Number - T06EL00641
Permit Status: Expired
Permit Description: REPAIR: ELECTRIC SYSTEM
| Start Date | Submittal | Complete Date | Status |
|---|---|---|---|
| 04/06/2006 | ELECTRICAL | 04/06/2006 | COMPLETED |
Outstanding Activity Conditions
Permit Number - T06EL00641
Permit Status: Expired
Permit Description: REPAIR: ELECTRIC SYSTEM
Total Outstanding Activity Conditions - 1
| Date | Name |
|---|---|
| 04/06/2006 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Outstanding Inspections
Permit Status: Expired
Permit Number: T06EL00641
Permite Description: REPAIR: ELECTRIC SYSTEM
Total Outstanding Inspections - 2
| Last Inspection Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/24/2006 | ELECTRIC - SERVICE UPGRADE | N/A | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* |
| 04/24/2006 | ELECTRIC - FINAL | N/A | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. BREAKER LABELING TO BE PERMANENT. 2. GROUND RODS NOT TO BE IN PARALLEL 3. SHEET METAL SCREWS NOT ALLOWED FOR GROUNDING. 4. ONLY ONE CONDUCTOR PER LUG TERMINATION - BREAKER ALSO. 5. CLEAN SURFACE UNDER LUGS. 6. FINISH PREVIOUS ITEMS 1-4 & 8-9 7. PLEASE VERIFY QUALIFIED ELECTRICIAN DOING WORK |