Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

The login landing page when selecting 'View' is still occurring and is still pending further investigation. 

Permit Details

Status:
Expired
Type:
SINGLE FAMILY OTHER
Address:
5511 E BURNS ST
Address NEW:
5511 E BURNS ST
Apply Date:
04/06/2006
Applicant:
PICCARRETA CARL A & GRACE R JT/RS
Description:
REPAIR: ELECTRIC SYSTEM

Permit Reviews

Permit Number - T06EL00641
Permit Status: Expired
Permit Description: REPAIR: ELECTRIC SYSTEM
Start Date Submittal Complete Date Status  
04/06/2006 ELECTRICAL 04/06/2006 COMPLETED Review Details

Outstanding Activity Conditions

Permit Number - T06EL00641
Permit Status: Expired
Permit Description: REPAIR: ELECTRIC SYSTEM
Total Outstanding Activity Conditions - 1
Date Name
04/06/2006 PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION.

Outstanding Inspections

Permit Status: Expired
Permit Number: T06EL00641
Permite Description: REPAIR: ELECTRIC SYSTEM
Total Outstanding Inspections - 2
Last Inspection Date Description Inspector Results Comments
04/24/2006 ELECTRIC - SERVICE UPGRADE N/A Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
04/24/2006 ELECTRIC - FINAL N/A Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. BREAKER LABELING TO BE PERMANENT.
2. GROUND RODS NOT TO BE IN PARALLEL
3. SHEET METAL SCREWS NOT ALLOWED FOR GROUNDING.
4. ONLY ONE CONDUCTOR PER LUG TERMINATION -
BREAKER ALSO.
5. CLEAN SURFACE UNDER LUGS.
6. FINISH PREVIOUS ITEMS 1-4 & 8-9
7. PLEASE VERIFY QUALIFIED ELECTRICIAN DOING WORK

Documents

File Name Document Type  
None DOCUMENTS VIEW