Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
04/24/2006 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. BREAKER LABELING TO BE PERMANENT.
2. GROUND RODS NOT TO BE IN PARALLEL
3. SHEET METAL SCREWS NOT ALLOWED FOR GROUNDING.
4. ONLY ONE CONDUCTOR PER LUG TERMINATION -
BREAKER ALSO.
5. CLEAN SURFACE UNDER LUGS.
6. FINISH PREVIOUS ITEMS 1-4 & 8-9
7. PLEASE VERIFY QUALIFIED ELECTRICIAN DOING WORK
04/07/2006 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
1. ENTRANCES THROUGH METER SECTION NOT ALLOWED BY MANUFACTURER.
2. MAINTAIN WORKING CLEARANCES IN FRONT OF SERVICE.
3. PLEASE LABEL ALL BREAKERS.
4. USE AN APPROVED FITTING AT LB
5. VERIFY 2ND GROUND ROD
6. GROUNDING ELECTRODE SYSTEM TO BE CONTINUOUS TO BOSS.
7. USE AN APPROVED LUG TERMINAL FOR NEUTRAL CONDUCTOR TO NOT FORK OR SPLIT.
8. PLEASE VERIFY GAS & WATER BONDING.
9. BOND JUNCTION BOXES ENCLOSURE.
10. SEPARATE GROUDING AND NEUTRALS AT SUB-PANEL.
11. SECURE GROUNDING ELECTRODE CONDUCTOR TO BUILDING.